yDO!BOOKEƒy[ƒWƒŠƒ“ƒNz
fi-1@@@230 / 521

BOOK‚ð‚Ý‚é

10•bŒã‚ÉBOOK‚̃y[ƒW‚Ɉړ®‚µ‚Ü‚·


ATEX –{Ž¿ˆÀ‘S–h”šiŒ`”Ô A2j 0344@KEMA 07ATEX0200 X IP66/IP67 II 1 G Ex ia IIC T4 Ga -30Ž…Tamb…+60Ž Tprocess = 105Ž ELECTRICAL PARAMETERS: Ui = 30 V, Ii = 93 mA, Pi = 1 W, Ci = 5 nF, Li = 0.5 mH II 1 D Ex ia IIIC T105Ž Da -30Ž…Tamb…+60Ž Tprocess = 105Ž II 3 G Ex ic IIC T4 Gc -30Ž…Tamb…+60Ž Tprocess = 110Ž ELECTRICAL PARAMETERS: Ui = 30 V, Ci = 5 nF, Li = 0.5 mH NEPSI ‘ψ³–h”šiŒ`”Ô N1j Ex d IIC T6 DIP A21 TA 85Ž Tprocess=80Ž -40Ž…Tamb…+75Ž Ex d IIC T5 DIP A21 TA 100Ž Tprocess=95Ž -40Ž…Tamb…+80Ž Ex d IIC T4 DIP A21 TA 115Ž Tprocess=110Ž -40Ž…Tamb…+80Ž ENCLOSURE TYPE IP66/IP67 NEPSI –{Ž¿ˆÀ‘S–h”šiŒ`”Ô N2j Ex ia IIC T4 Tprocess=105Ž -40Ž…Tamb…+60Ž Enclosure IP66/IP67 ELECTRICAL PARAMETERS: Ui=30V, Ii=100mA, Pi=1W, Ci=13nF, Li=0.5mH NEPSI Type n –h”šiŒ`”Ô N5j Ex nL IIC T4 Tprocess=110Ž -40Ž…Tamb…+60Ž Enclosure IP66/IP67 ELECTRICAL PARAMETERS: Ui=30V, Ii=100mA, Pi=1W, Ci=13nF, Li=0.5mH IECEx ‘ψ³–h”šiŒ`”Ô E1j Certificate No. IECEx KEM 08.0001 X IP66/IP67 Ex d IIC T6 Ga/Gb -30Ž…Tamb…+75Ž Tprocess…85Ž Ex d IIC T5 Ga/Gb -30Ž…Tamb…+80Ž Tprocess…100Ž Ex d IIC T4 Ga/Gb -30Ž…Tamb…+80Ž Tprocess…110Ž Ex tb IIIC T85Ž Db -30Ž…Tamb…+75Ž Tprocess…85Ž Ex tb IIIC T100Ž Db -30Ž…Tamb…+75Ž Tprocess…100Ž Ex tb IIIC T110Ž Db -30Ž…Tamb…+75Ž Tprocess…110Ž Caution - Use supply wires suitable for 5Ž above surrounding ambient IECEx –{Ž¿ˆÀ‘S–h”šiŒ`”Ô E2j IECEx KEM 07.0058X IP66/IP67 Ex ia IIC T4 Ga -30Ž…Tamb…+60Ž Tprocess = 105Ž ELECTRICAL PARAMETERS: Ui = 30 V, Ii = 93 mA, Pi = 1 W, Ci = 5 nF, Li = 0.5 mH Ex ia IIIC T105Ž Da -30Ž…Tamb…+60Ž Tprocess = 105Ž Ex ic IIC T4 Gc -30Ž…Tamb…+60Ž Tprocess = 110Ž ELECTRICAL PARAMETERS: Ui = 30 V, Ci = 5 nF, Li = 0.5 mH 5 1 10 WEBƒT[ƒrƒX»•i‚ÌÅVî•ñ‚Íwww.azbil.com/jp/