Infilex GC/GD/AC/ZM
Compact but Powerful!
| Description | Multi-purpose Controller Infilex GC | Multi-purpose Data Gathering Panel Infilex GD | |||||
| External view |
|
|
|||||
| Model number | WY5511/5311/5111 | WY5510/5310/5110 | |||||
| Power | 100 to 240VAC | ||||||
| Communication | IP/LonTalk®/NC-bus(4800bps) | ||||||
| Environmental condition |
Ambient temperature |
0 to 50°C | |||||
| Ambient humidity |
10 to 90%RH | ||||||
| Vibration and shock |
5.9m/s2 (0.6G)max. (10 to 150Hz) | ||||||
| Size (mm) | 60(IP:120)W x 140H x 90D(basic) 30W x 140H x 90D(I/O) |
||||||
| Installation method | DIN rail / direct screw mounting | ||||||
| Terminal block | Screwless clamp terminal block
(IO / communication) M3 screw terminal (Power supply) |
||||||
| Signal input & output |
AI | Pt100Ω/0-10V/2-10V/0-5V/1-5V/4-20mA | |||||
| AO | 0-10V/2-10V/0-5V/1-5V/4-20mA | ||||||
| DI | Dry contact | ||||||
| DO | Dry relay | ||||||
| Description | AHU Controller Infilex AC |
Zone Manager Infilex ZM | |||||
| External view |
|
|
|||||
| Model number | WY5517/5317/5117 | WY5522/5322/5122 | |||||
| Power | 24VAC | 100 to 240VAC | |||||
| Communication | IP/LonTalk®/NC-bus(4800bps) | ||||||
| Environmental condition |
Ambient temperature |
0 to 50°C | |||||
| Ambient humidity |
10 to 90%RH | ||||||
| Vibration and shock |
5.9m/s2 (0.6G)max. (10 to 150Hz) |
||||||
| Size (mm) | 60(IP:120)W x 140H x 90D(basic) 30W x 140H x 90D(I/O) |
60(IP:120)W x 140H x 90D | |||||
| Installation method | DIN rail / direct screw mounting | ||||||
| Terminal block | Screwless clamp terminal block
(IO / communication) M3 screw terminal (Power supply) |
||||||
| Signal input & output |
AI | Pt100Ω/1-5V | - | ||||
| AO | 0-10V/2-10V | - | |||||
| DI | Dry contact | - | |||||
| DO | Dry relay | - | |||||
Application

* Infilex , savic-net and Neopanel are trademarks or registered trademarks of Azbil Corporation in Japan or in other countries.