SDC45V/46V Digital Indicating Controller with Multi-Input Computation Function

SDC45V/46V Digital Indicating Controller with Multi-Input Computation Function
The DigitroniK SDC45V/46V is a highly advanced, high-precision compact digital indicating controller, featuring a 5-digit indicator, an input sampling cycle of 100 ms, indication accuracy of ±0.1%* of reading, and either 2 full multi-range analog inputs or 1 full multi-range input plus 2 DC current/voltage inputs. A dual-input computation function can be used for each input and output processing unit, allowing sensor input changeover, control based on the average of 2 PV values, control output changeover, feed-forward control, override control, etc. In addition, the input processing unit has a temperature-pressure correction function (2-input model: temperature correction or pressure correction).

*A representative figure. Indication accuracy differs depending on the input range type and temperature band.


  • Dual-input computation capability and temperature-pressure correction are built in.
  • The number of analog inputs, either two (full multi) or three (1 full multi and 2 DC current/voltage), can be selected (by model number).
  • Control, ranging from cascade to backup control, is available for 1 or 2 loops.
  • Sampling cycle of 100 ms and accuracy of ±0.1% rdg.
  • Ample room for indication of vital information on dual 7-segment, 5-digit LED displays and an auxiliary 11-segment, 3-digit LED display
  • Heat/cool control, using two control outputs
  • Using the optional transmitter power supply function, a pressure transmitter can be directly connected.
  • IP65 protection for the front panel
  • Up to 16 recipe settings involving SP, event settings, etc., and 8 groups of fixed-value control output settings support automatic operation of equipment.
  • Support for nonlinear processes using input/output broken line linear approximation tables
  • Customizable parameter keys and LED
  • A variety of inputs and outputs:
    2 inputs, 7 outputs, 14 DIs, 8 DOs, 2 CT or AT inputs, RS-485 communications

Specifications

PV1 input Type Thermocouple, RTD, DC current/voltage
Range (Refer to "Input types and ranges.")
PV2 input
(2-input model)
Type Thermocouple, RTD, DC current/voltage
Range (Refer to "Input types and ranges.")
PV21
(3-input model)
Type DC current/voltage
Range 0?20 mA, 4?20 mA, 0?5 V, 1?5 V and 0?10 V
PV22
(3-input model)
Type DC voltage
Range 0?5 V, 1?5 V and 0?10 V
PV input Sampling cycle 100 ms
Indication Type 5-digit, 7-segment and 3-digit, 11-segment digital displays
Accuracy ±0.1 % rdg ±1 digit (depending on range)
Output No. of outputs SDC45V: 5 max., SDC46V: 7 max.
Type Relay, voltage pulse, DC current and voltage, motor drive, power supply for signal transmitter (24 Vdc)
Control mode PID (direct action, reverse action, heat/cool)
No. of PID groups 16
Auto-tuning Automatic PID settings by limit cycle method (3 types)
DI No. of inputs SDC45V: 10 max., SDC46V: 14 max.
Function LSP change, READY/RUN changeover, indication changeover, etc.
DO No. of outputs 8 max.
Function Process value, set value, deviation value, device alarm, etc.
Communications Type RS-485
No. of connected units 31 max.
Speed 38400 bps max.
General Power AC power model: 100 to 240 Vac, 50/60 Hz,
DC power model: 24 Vdc
Power consumption SDC45V: 30 VA max. (AC power model), 12 W max (DC power model)
SDC46V: 40 VA max. (AC power model), 15 W max (DC power model)
Battery life 3 years without connection to power (at 20 °C ambient temperature)
Certification CE marking
Front panel protection IP65
Mass SDC45V: 400 g max. SDC46V: 700 g max.

Input types and ranges

Sensor Sensor type Range

Thermocouple

K -270.0 to +1372.0 °C
E -270.0 to +1000.0 °C
J -200.0 to +1200.0 °C
T -270.0 to +400.0 °C
B 0.0 to 1800.0 °C
R -50.0 to +1768.0 °C
S -50.0 to +1768.0 °C
W(WRe5-26 ) 0.0 to 2300.0 °C
PR40-20 0.0 to 1900.0 °C
Ni-Ni·Mo 0.0 to 1300.0 °C
N -200.0 to +1300.0 °C
PL II 0.0 to 1390.0 °C
DIN U -200.0 to +600.0 °C
DIN L -200.0 to +900.0 °C
Gold-iron/Chromel -273.0 to +27.0 °C

RTD

Pt100 -200.0 to +850.0 °C
-200.00 to +300.00 °C
JPt100 -200.0 to +640.0 °C
-200.00 to +300.00 °C

DC current/voltage
(-19999 to +32000 U)

Current 4 to 20 mA
0 to 20 mA
Voltage 0 to 10 mV
-10 to +10 mV
0 to 100 mV
-100 to +100 mV
0 to 1 V
-1 to +1 V
1 to 5 V
0 to 5 V
0 to 10 V

Catalog for SDC45V (sdc45v_e)

Catalog for SDC46V (sdc46v_e)

Specification Sheet (CP-SS-1848E)

User's Manual for Installation (CP-UM-5445E)

User's Manual for Displays and Settings (CP-SP-1265E)

User's Manual for Computational Functions (CP-SP-1275E)

User's Manual for SLP-C45 Smart Loader Package (CP-UM-5458E)