Azbil Corporation No. SS2-8113-0320 - 3 - Leakage specification Contoured type plug IEC 60534-4:2006 or JIS B 2005-4:2008 Standard....Class IV: Leakage less than 0.01% Option.......Leakage less than 0.001% of maximum valve capacity. Quick opening plug Leakage less than 0.00001% of maximum valve capacity. Hysteresis error Without positioner :Within 3% F.S. (Within 5% F.S.) ((Within 9% F.S.)) With positioner : Within 1% F.S. ((Within 2% F.S.)) Linearity Without positioner :Within ±5% F.S. ((Within 9% F.S.)) With positioner : Within ±1% F.S. (VPE : Within ±3% F.S., HEP : Within ±2% F.S.) ((Within 2% F.S.)) Note) 1) When positioner is not provided, operating performance may vary depending on type of packing used. 2) Parenthesized figures are applicable to Type PSA1. 3) Double parenthesized figures are applicable to type PSA6R. Dimensions Refer to Figure 5, Table 17, and Table 18. Weight: Refer to Table 19 and Table 20. Actuator orientation: Refer to Figure 6. Finish Blue (Munsell 10B5/10) or silver or other specified colors Table 1 Combination of the nominal size, flange size and jacket connection size Nominal size (inches) 1. 2 2. 3 4 6 Flange size (inches) Semi-jacket 1. 2 2. 3 4 6 Full-jacket 2. 3 4 5 6 8 Jacket connection size (inches) Flange type 1/2, 3/4 1/2, 3/4, 1 Screwed type 1/2, 3/4 Table 2 Body/trim material combinations and operating temperature ranges range (°C) Body material Trim material JIS SCPH2 SCS13A SCS14A ASTM A216WCB A351CF8 A351CF8M JIS SUS304 0 to +300 0 to +300 JIS SUS316 0 to +300 0 to +300 0 to +300 JIS SUS304L 0 to +300 JIS SUS316L 0 to +300 0 to +300 JIS SUS329J1 0 to +300 JIS SUS304 Stellite 0 to +425 0 to +550 JIS SUS304 Stellite face 0 to +425 0 to +550 JIS SUS316 Stellite 0 to +425 0 to +550 0 to +550 JIS SUS316 Stellite face 0 to +425 0 to +550 0 to +550 JIS SUS304L Stellite 0 to +550 JIS SUS316L Stellite 0 to +450 0 to +450 JIS SUS329J1 Stellite 0 to +550 Note) “ ” shows standard combination of valve body and trim materials. 1 7