【DO!BOOK・ページリンク】 cv-01 113 / 168 10秒後にBOOKのページに移動します |
|
No. SS2-8113-0320 Azbil Corporation - 8 - Allowable differential pressure Contoured-type metal seat (%CF, LCF, %C, LC) : PTFE packing Valves with type DAP actuator Note) 1) When a backup sysytem for pressure drop at the air source is used, select the allowable differential pressure from whichever is lower-constant supplied air pressure or backup sysytem set pressure (trip pressure). 2) ..: Positioner is necessary. 3) Take care not to cause the maximum allowable differential pressure to exceed the maximum operating pressure designated by ANSI B16. 34-1981 or JIS B2201-1984. 4) The upper figures denote the operating allowable differential pressure. The lower denote allowable differential pressure at full closure. Table 8 Air-to-open and Air-to-close Actuator Model No. Supply Pressure kPa {kgf/cm2} Positioner Differential Pressure (by port size(inches)) kPa {kgf/cm2} 2. 3 4 5 6 DAP560 290 {3.0} .. 3920 {40.0} 3610 {36.8} 2030 {20.7} 1290 {13.2} 780 5100 {8.0} {52.0} 390 {4.0} 3920 {40.0} 3920 {40.0} 2730 {27.8} 1740 {17.8} 1060 5100 {10.8} {52.0} 4800 {49.0} 490 {5.0} 3920 {40.0} 3920 {40.0} 3420 {34.9} 2200 {22.4} 1330 5100 {13.6} {52.0} 5100 {52.0} DAP1000 290 {3.0} 3920 {40.0} 3920 {40.0} 3620 {36.9} 2310 {23.6} 1410 5100 {14.4} {52.0} 5100 {52.0} 390 {4.0} 3920 {40.0} 3920 {40.0} 3920 {40.0} 3120 {31.8} 1890 5100 {19.3} {52.0} 5100 {52.0} 4800 {49.0} 490 {5.0} 3920 {40.0} 3920 {40.0} 3920 {40.0} 3920 {40.0} 2380 5100 {24.3} {52.0} 5100 {52.0} 5100 {52.0} DAP1500 290 {3.0} 3480 {35.5} 2120 {21.6} 390 {4.0} 3920 {40.0} 2840 4610 {29.0} {47.0} 490 {5.0} 3920 {40.0} 3570 5100 {36.4} {52.0} |