Azbil Corporation No. SS2-8113-0320 - 11 - Contoured-type metal seat (%CF, LCF, %C, LC) Valves with type DAP actuator Note) 1) When a backup sysytem for pressure drop at the air source is used, select the allowable differential pressure from whichever is lower-constant supplied air pressure or backup sysytem set pressure (trip pressure). 2) ..: Positioner is necessary. 3) Take care not to cause the maximum allowable differential pressure to exceed the maximum operating pressure designated by ANSI B16. 34-1981 or JIS B2201-1984. 4)The upper figures denote the operating allowable differential pressure. The lower denote allowable differential pressure at full closure. Table 13 Air-to-open and Air-to-close Actuator Model No. Supply Pressure kPa {kgf/cm2} Positioner Differential Pressure (by port size(inches)) kPa {kgf/cm2} 2. 3 4 5 6 DAP560 290 {3.0} .. 3920 {40.0} 3430 {34.9} 1490 {15.1} 950 {9.6} 580 4770 {5.9} {48.6} 390 {4.0} 3920 {40.0} 3920 {40.0} 2210 {22.5} 1410 {14.3} 860 5100 {8.7} {52.0} 4800 {49.0} 490 {5.0} 3920 {40.0} 3920 {40.0} 2920 {29.7} 1870 {19.0} 1140 5100 {11.6} {52.0} 5100 {52.0} DAP1000 290 {3.0} 3920 {40.0} 3920 {40.0} 2540 {25.9} 1620 {16.5} 990 5100 {10.0} {52.0} 5100 {52.0} 390 {4.0} 3920 {40.0} 3920 {40.0} 3740 {38.1} 2390 {24.3} 1460 5100 {14.8} {52.0} 5100 {52.0} 490 {5.0} 3920 {40.0} 3920 {40.0} 3920 {40.0} 3170 {32.3} 1930 5100 {19.6} {52.0} 5100 {52.0} 4950 {50.4} DAP1500 290 {3.0} 2490 {25.3} 1520 {15.5} 390 {4.0} 3680 {37.5} 2250 {22.9} 490 {5.0} 3920 {40.0} 2970 4870 {30.2} {49.6} 1 7 |