Azbil Corporation No. SS2-8113-0320 - 13 - Contoured-type metal seat (%CF, LCF, %C, LC): Graphite packing “P6610CH+M8590” (+500 to +566 °C) Valves with type DAP actuator Note) 1) When a backup sysytem for pressure drop at the air source is used, select the allowable differential pressure from whichever is lower-constant supplied air pressure or backup sysytem set pressure (trip pressure). 2) ..: Positioner is necessary. 3) Take care not to cause the maximum allowable differential pressure to exceed the maximum operating pressure designated by ANSI B16. 34-1981 or JIS B2201-1984. 4)The upper figures denote the operating allowable differential pressure. The lower denote allowable differential pressure at full closure. Table 16 Air-to-open and Air-to-close Actuator Model No. Supply Pressure kPa {kgf/cm2} Positioner Differential Pressure (by port size(inches)) kPa {kgf/cm2} 2. 3 4 5 6 DAP560 290 {3.0} .. 3590 {36.6} 2530 {25.7} 1420 {14.4} 910 {9.2} 580 {5.6} 390 {4.0} 3920 {40.0} 3800 {38.7} 2130 {21.7} 1360 {13.8} 830 5100 {8.4} {52.0} 490 {5.0} 3920 {40.0} 3920 {40.0} 2850 {29.0} 1820 {18.5} 1110 5100 {11.3} {52.0} 5070 {51.6} DAP1000 290 {3.0} 3920 {40.0} 3920 {40.0} 2410 {24.5} 1540 {15.7} 940 5100 {9.5} {52.0} 4300 {43.8} 390 {4.0} 3920 {40.0} 3920 {40.0} 3620 {36.9} 2320 {23.6} 1410 5100 {14.3} {52.0} 5100 {52.0} 490 {5.0} 3920 {40.0} 3920 {40.0} 3920 {40.0} 3090 {31.5} 1880 5100 {19.1} {52.0} 5100 {52.0} 4830 {49.2} DAP1500 290 {3.0} 3710 {37.8} 2370 {24.1} 1450 {14.7} 390 {4.0} 3920 {40.0} 3560 {36.3} 2170 5570 {22.1} {56.7} 490 {5.0} 3920 {40.0} 3920 {40.0} 2900 7430 {29.5} {75.7} 4750 {48.4} 1 7 |