【DO!BOOK・ページリンク】 cv-01 141 / 168 10秒後にBOOKのページに移動します |
|
No. SS2-8110-0300 Azbil Corporation - 4 - Allowable differential pressure Metal seat (%C, LC) : PTFE packing Note) 1. The figure inside bold line are for standard actuator. 2. Positioner; ..... without, .....with Table 2 Air-to-close Actuator model No. Supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Positioner Differential pressure kPa {kgf/cm2} Port size (inches) 1 1. 1. 2 2. 3 4 5 6 8 10 12 VA1D 120 {1.2} 20 to 98 {0.2 to 1.0} .. 740 {7.5} 460 {4.7} 300 {3.1} 180 {1.8} --- --- 140 {1.4} 20 to 98 {0.2 to 1.0} .. 1860 {19.0} 1180 {12.0} 770 {7.9} 460 {4.7} --- --- 250 {2.6} 20 to 98 {0.2 to 1.0} .. 3920 {40.0} 3920 {40.0} 3820 {39.0} 2260 {23.0} --- --- VA2D 120 {1.2} 20 to 98 {0.2 to 1.0} .. 981 {10.0} 670 {6.8} 440 {4.5} 250 {2.6} 160 {1.6} 110 {1.1} 60 {0.6} 140 {1.4} 20 to 98 {0.2 to 1.0} .. 2650 {27.0} 1670 {17.0} 1080 {11.0} 670 {6.8} 410 {4.2} 290 {3.0} 170 {1.7} 250 {2.6} 20 to 98 {0.2 to 1.0} .. 3920 {40.0} 3920 {40.0} 3920 {40.0} 3330 {34.0} 2060 {21.0} 1470 {15.0} 830 {8.5} --- --- VA3D 120 {1.2} 20 to 98 {0.2 to 1.0} .. 1670 {17.0} 1080 {11.0} 720 {7.4} 430 {4.4} 260 {2.7} 190 {1.9} 110 {1.1} 70 {0.7} 40 {0.4} 140 {1.4} 20 to 98 {0.2 to 1.0} .. 3920 {40.0} 2740 {28.0} 1860 {19.0} 1080 {11.0} 690 {7.0} 490 {5.0} 270 {2.8} 180 {1.8} 120 {1.2} 250 {2.6} 20 to 98 {0.2 to 1.0} .. 3920 {40.0} 3920 {40.0} 3920 {40.0} 3920 {40.0} 3430 {35.0} 2450 {25.0} 1370 {14.0} 890 {9.1} 620 {6.3} VA4D 120 {1.2} 20 to 98 {0.2 to 1.0} .. --- --- --- --- 370 {3.8} 260 {2.7} 150 {1.5} 98 {1.0} 60 {0.6} 38 {0.39} --- --- 140 {1.4} 20 to 98 {0.2 to 1.0} .. --- --- --- --- 960 {9.8} 690 {7.0} 380 {3.9} 240 {2.5} 170 {1.7} 97 {0.99} --- --- 250 {2.6} 20 to 98 {0.2 to 1.0} .. --- --- --- --- 3920 {40.0} 3430 {35.0} 1860 {19.0} 1180 {12.0} 860 {8.8} 480 {4.9} --- --- VA5D 120 {1.2} 20 to 98 {0.2 to 1.0} .. --- --- --- --- --- --- --- 130 {1.3} 90 {0.9} 52 {0.53} 33 {0.34} 22 {0.23} 140 {1.4} 20 to 98 {0.2 to 1.0} .. --- --- --- --- --- --- --- 330 {3.4} 240 {2.4} 130 {1.3} 85 {0.87} 59 {0.60} 250 {2.6} 20 to 98 {0.2 to 1.0} .. --- --- --- --- --- --- --- 1670 {17.0} 1180 {12.0} 670 {6.8} 420 {4.3} 290 {3.0} |