Azbil Corporation No. SS2-8110-0300 - 7 - Note) 1. * The allowable differential pressure for 40 to 200 kPa {0.4 to 2.0 kgf/cm2} spring range are the same as for 40 to 120 kPa {0.4 to 1.2 kgf/cm2} spring. 2. The figures inside bold line are for standard actuator. 3. Positioner; ..... without, ..... Preferably with, .....with Table 5 Air-to-open Actuator model No. Supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Positioner Differential pressure kPa {kgf/cm2} Port size (inches) 1 1. 1. 2 2. 3 4 5 6 8 10 12 VA1R 140 {1.4} 20 to 98 {0.2 to 1.0} .. or .. 370 {3.8} 170 {1.7} 60 {0.6} --- --- --- --- 40 to 120 {0.4 to 1.2} * .. 1430 {14.6} 860 {8.8} 550 {5.6} 280 {2.9} --- --- --- 270 {2.8} 80 to 240 {0.8 to 2.4} .. 2620 {26.7} 1850 {18.9} 1540 {15.7} 900 {9.2} --- --- --- VA2R 140 {1.4} 20 to 98 {0.2 to 1.0} .. or .. 780 {8.0} 430 {4.4} 240 {2.5} 10 {1.0} 98 {0.1} --- --- 40 to 120 {0.4 to 1.2} * .. 1820 {18.6} 1430 {14.6} 960 {9.8} 540 {5.5} 290 {3.0} 190 {1.9} 70 {0.7} 270 {2.8} 80 to 240 {0.8 to 2.4} .. 2940 {30.0} 2680 {27.3} 1990 {20.3} 1430 {14.6} 860 {8.8} 610 {6.2} 310 {3.2} --- --- VA3R 140 {1.4} 20 to 98 {0.2 to 1.0} .. or .. --- --- 660 {6.7} 350 {3.6} 180 {1.8} 98 {1.0} 20 {0.2} --- --- 40 to 120 {0.4 to 1.2} * .. --- --- 1760 {18.0} 981 {10.0} 650 {6.6} 450 {4.6} 220 {2.3} 120 {1.2} 70 {0.7} 270 {2.8} 80 to 240 {0.8 to 2.4} .. --- --- 2940 {30.0} 2160 {22.0} 1590 {16.2} 1140 {11.6} 630 {6.4} 380 {3.9} 250 {2.6} VA4R 140 {1.4} 20 to 98 {0.2 to 1.0} .. or .. --- --- --- --- 330 {3.4} 220 {2.2} 90 {0.9} 40 {0.4} --- --- --- --- 40 to 120 {0.4 to 1.2} * .. --- --- --- --- 981 {10.0} 710 {7.2} 360 {3.7} 220 {2.2} 140 {1.4} 60 {0.6} --- --- 270 {2.8} 80 to 240 {0.8 to 2.4} .. --- --- --- --- 2260 {23.0} 1670 {17.0} 930 {9.5} 580 {5.9} 390 {4.0} 200 {2.0} --- --- VA5R 140 {1.4} 20 to 98 {0.2 to 1.0} .. or .. --- --- --- --- --- --- --- 90 {0.9} 50 {0.5} --- --- --- 40 to 120 {0.4 to 1.2} * .. --- --- --- --- --- --- --- 340 {3.5} 220 {2.2} 110 {1.1} 50 {0.5} 30 {0.3} 270 {2.8} 80 to 240 {0.8 to 2.4} .. --- --- --- --- --- --- --- 840 {8.6} 570 {5.8} 300 {3.1} 190 {1.9} 120 {1.2} PSA6R 400 {4.0} 200 to 340 {2.0 to 3.5} .. --- --- --- --- --- --- --- --- --- 580 {5.9} --- --- 500 {5.0} 200 to 390 {2.0 to 4.0} .. --- --- --- --- --- --- 2530 {25.8} 1780 {18.2} 981 {10.0} --- 380 {3.9} 260 {2.7} 1 9 |