【DO!BOOK・ページリンク】 cv-01 26 / 168 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-AGV200-0001 - 23 - 5. Accessories 5-1 Hand wheel Use: The manual hand wheel enables you to open and close the valve manually. Orientation: Side hand wheel, which is mounted to the yoke of the actuator. 5-2 Positioner Use: In response to input signals from the controller, the positioner controls the valve accurately and swiftly, switches between direct and reverse operation, and changes valve characteristics. Models: According to input signals and applications, select one of the models shown below. Figure 16 Side hand wheel Model AVP70X/30X Smart valve positioner Input signal: AVP300 4 to 20mADC (Any split range is available) AVP301 4 to 20mADC (with travel transmission) AVP701 HART communication protocol (with travel transmission) AVP702/302 HART communication protocol AVP703 FoundationTM fieldbus Common Model: JIS C 0920 water-proof NEMA TYPE4X, IP66 Approval: TIIS Flameproof, FM Explosionproof, FM Intrinsically safe, CSA Explosionproof, ISSeP/ATEX Flameproof, KEMA/ ATEX Intrinsically safe HEP model Single acting pneumatic positioner HEP 15: JIS Flameproof HEP 16: JIS Intrinsically Safe HEP 17: JIS Safe water-proof HEP 18: FM intrinsically safe HEP 19: FM intrinsically safe Input signal: 4 to 20mA DC Half range: (4 to 12 or 12 to 20mA DC) Note) In the photograph, the pressure regulator is attached. VPE 04/05 model Single acting pneumatic positioner Input signal: 0.2 to 1.0 kgf/cm2 20 to 100 kPa and half range Note) Usable with PSA1 only. HTP model Single acting pneumatic positioner Input signal: 0.2 to 1.0 kgf/cm 20 to 100 kPa and half range 1 1 |