Azbil Corporation No. SS2-8113-0200 - 3 - Performance Rated Cv value Refer to Table 2. Flow characteristics Refer to Figure 1. Inherent rangeability Refer to Table 2. . Optional; 75 : 1 for rated Cv 1.0 to 14 Allowable differential pressure Refer to Table 8 to Table 13. Leakage specifications . Contoured type plug IEC 60534-4:2006 or JIS B 2005-4:2008 Standard..... Class IV: Leakage less than 0.01% of maximum valve capacity. Option........ Leakage less than 0.001% of maximum valve capacity. Class VI: Leakage less than 0.00001% of maximum valve capacity. . Quick opening type plug Leakage less than 0.00001% of maximum valve capacity Hysteresis error Without positioner: Within 3% F.S. (Within 5% F.S.) With positioner: Within 1% F.S. Linearity Without positioner: Within ± 5% F.S. With positioner: Within ± 1% F.S. (VPE: Within ±3% F.S., AVP&HEP: Within ± 2% F.S.) Note) 1) When positioner is not provided, operating performance may vary depending on types of packings used. 2) Parenthesized figures are applicable to Type PSA1. Dimensions Refer to Figure 6, Table 18 and Table 19. Weight Refer to Table 20, Table 21 and Table 22. Actuator orientation Refer to Figure 6. Finish Blue (Munsell 10B5/10) or silver, or other specified colors. 1 2