【DO!BOOK・ページリンク】 cv-01 39 / 168 10秒後にBOOKのページに移動します |
|
No. SS2-8113-0200 Azbil Corporation - 8 - Allowable differential pressure Contoured-type metal seat (%CF, LCF) : PTFE packing Table 8 Air-to-close Actuator Model No. Supply Pressure kPa{kgf/ cm2} Spring range kPa {kgf/ cm2} Positioner Differential pressure {by Cv value} kPa {kgf/cm2} Below 0.1 0.16 to 0.25 0.4 0.63 1.0 1.6 2.5 4.0 6.3 10 14 PSA1D 140 {1.4} 20 to 98 {0.2 to 1.0} .. 3920* {40.0} 3040 {31.0} 3040 {31.0} 1570 {16.0} 1570 {16.0} 981 {10.0} 981 {10.0} 550 {5.6} 410 {4.2} 250 5490 {2.6} {56.0} 160 {1.6} 20 to 98 {0.2 to 1.0} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 2740 {28.0} 2060 {21.0} 1270 9810 {13.0} {100} 9810 {100} 9810 {100} 8240 {84.0} 8240 {84.0} 5100 {52.0} 5100 {52.0} 390 {4.0} 80 to 240 {0.8 to 2.4} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3820 9810 {39.0} {100} 9810 {100} 9810 {100} 8240 {84.0} 6180 {63.0} HA2D 140 {1.4} 20 to 98 {0.2 to 1.0} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3200 {32.6} 3200 {32.6} 1960 {20.0} 1960 {20.0} 1070 {10.9} 800 {8.2} 490 9810 {5.0} {100} 6080 {62.0} 6080 {62.0} 160 {1.6} 20 to 98 {0.2 to 1.0} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 2470 9810 {25.2} {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 5300 {54.0} 390 {4.0} 80 to 240 {0.8 to 2.4} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 9810 {100} 9810 {100} 9810 {100} 7350 {75.0} |