Azbil Corporation No. SS2-8113-0200 - 9 - Note) 1) ..: Positioner is necessary, ..: Can be operated either with or without positioner. 2) Take care not to cause the maximum allowable differential pressure to exceed the maximum operating pressure designated by ANSI B 16. 34-1981 or JIS B2201-1984. 3) The upper figures denote the operating allowable differential pressure. The lower denote allowable differential pressure at full closure. 4) When liquid service the operating allowable differential pressure with an asterisk(*) should be read as 2940 kPa {30 kgf/cm2}. When operating differential pressure of liquid exceeds 2940 kPa {30 kgf/cm2}, use model HLC. (Refer to the Specification sheet No.SS2-8113-0210.) Table 9 Air-to-open Actuator Model No. Supply pressure kPa{kgf/ cm2} Spring range kPa{kgf/ cm2} Positioner Differential pressure {by Cv value} kPa {kgf/cm2} Below 0.1 0.16 to 0.25 0.4 0.63 1.0 1.6 2.5 4.0 6.3 10 14 PSA1R 140 {1.4} 20 to 98 {0.2 to 1.0} .. 3920* {40.0} 3040 {31.0} 3040 {31.0} 1570 {16.0} 1570 {16.0} 981 {10.0} 981 {10.0} 550 {5.6} 410 {4.2} 250 5490 {2.6} {56.0} 270 {2.8} 80 to 240 {0.8 to 2.4} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3820 {39.0} 2840 {29.0} 1760 9810 {18.0} {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 7060 {72.0} 7060 {72.0} HA2R 140 {1.4} 20 to 98 {0.2 to 1.0} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3200 {32.6} 3200 {32.6} 1960 {20.0} 1960 {20.0} 1070 {10.9} 800 {8.2} 490 9810 {5.0} {100} 6080 {62.0} 6080 {62.0} 270 {2.8} 80 to 240 {0.8 to 2.4} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920 {40.0} 3430 9810 {35.0} {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 7450 {75.9} 5490 {56.0} 1 2 |