Azbil Corporation No. SS2-8113-0200 - 11 - Contoured type metal seat (%CF, LCF) : Graphite packing “P6610CH+P6528”(+230 to +500 °C) Note) 1) ..: Positioner is necessary. 2) Take care not to cause the maximum allowable differential pressure to exceed the maximum operating pressure designated by JIS B 2201-1984 or ANSI B 16.34-1981. 3) The upper figures denote the operating allowable differential pressure. The lower denote allowable differential pressure at full closure. 4) When liquid service, the operating allowable differential pressure with an asterisk(*) should be read as 2940 kPa {30 kgf/cm2}. When operating differential pressure of liquid exceeds 2940 kPa {30 kgf/cm2}, use model HLC. (Refer to the Specification sheet No.SS-8113-0210) Contoured type metal seat (%CF, LCF) : Graphite packing “P6610CH+M8590”(+500 to +560 °C) Note) 1) ..: Positioner is necessary. 2) Take care not to cause the maximum allowable differential pressure to exceed the maximum operating pressure designated by JIS B 2201-1984 or ANSI B 16.34-1981. 3) The upper figures denote the operating allowable differential pressure. The lower denote allowable differential pressure at full closure. 4) When liquid service, the operating allowable differential pressure with an asterisk(*) should be read as 2940 kPa {30 kgf/cm2}. When operating differential pressure of liquid exceeds 2940 kPa {30 kgf/cm2}, use model HLC. (Refer to the Specification sheet No.SS-8113-0210) Table 14 Air-to-close Actuator Model No. Supply Pressure kPa{kgf/ cm2} Spring range kPa{kgf/ cm2} Positioner Differential pressure {by Cv value} kPa {kgf/cm2} Below 0.1 0.16 to 0.25 0.4 0.63 1.0 1.6 2.5 4.0 6.3 10 14 HA1D 390 {4.0} 80 to 240 {0.8 to 2.4} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 6240 {63.6} Table 15 Air-to-open Actuator Model No. Supply Pressure kPa{kgf/ cm2} Spring range kPa{kgf/ cm2} Positioner Differential pressure {by Cv value} kPa {kgf/cm2} Below 0.1 0.16 to 0.25 0.4 0.63 1.0 1.6 2.5 4.0 6.3 10 14 HA1R 270 {2.8} 80 to 240 {0.8 to 2.4} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 2710 9810 {27.6} {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 5900 {60.1} 4400 {44.8} Table 16 Air-to-close Actuator Model No. Supply Pressure kPa{kgf/ cm2} Spring range kPa{kgf/ cm2} Positioner Differential pressure {by Cv value} kPa {kgf/cm2} Below 0.1 0.16 to 0.25 0.4 0.63 1.0 1.6 2.5 4.0 6.3 10 14 HA2D 390 {4.0} 80 to 240 {0.8 to 2.4} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9450 {96.3} 5840 {59.5} Table 17 Air-to-open Actuator Model No. Supply Pressure kPa{kgf/ cm2} Spring range kPa{kgf/ cm2} Positioner Differential pressure {by Cv value} kPa {kgf/cm2} Below 0.1 0.16 to 0.25 0.4 0.63 1.0 1.6 2.5 4.0 6.3 10 14 HA2R 270 {2.8} 80 to 240 {0.8 to 2.4} .. 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3920* {40.0} 3750 {38.2} 2310 9810 {23.5} {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9810 {100} 9260 {94.4} 5020 {51.1} 1 2 |