【DO!BOOK・ページリンク】 cv-01 48 / 168 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-8113-0210 - 3 - Note) 1) “ ” shows standard combination of value body and trim materials. 2) SUS440C is recommended for values for cavitation/flashing service of water or for superheated service of water higher than 100°C. 3) When rated Cv value is 0.16 or lower Stellite faced valve plugs or SUS440C valve plugs are standard. Note) 1) “..” denotes production ranges. 2) Please select model # HLS for values of rated Cv0.01, 0.04, 0.1 Table 1 Body/trim material combinations and operating temperature range (°C) Body material Trim material JIS SCPH2 SCPH21 SCPH61 SCS11 SCS13A SCS14A SCS16A SCS19A ASTM A216WCB A217WC6 A217C5 - A351CF8 A351CF8M A351CF3M A351CF3 JIS SUS440C -5 to +425 -5 to +425 -5 to +425 - - - - - JIS SUS304 Stellite -5 to +425 -5 to +550 -5 to +566 - -196 to +550 - - - JIS SUS304 Stellite face -5 to +425 -5 to +550 -5 to +566 - -196 to +550 - - - JIS SUS316 Stellite -5 to +425 -5 to +550 -5 to +566 - -196 to +550 -196 to +550 - - JIS SUS316 Stellite face -5 to +425 -5 to +550 -5 to +566 - -196 to +550 -196 to +550 - - JIS SUS304 L Stellite - - - - -196 to +550 - - -196 to +450 JIS SUS316 L Stellite - - - - -196 to +450 -196 to +450 -196 to +450 -196 to +450 JIS SUS329J1 Stellite -50 to +550 - -196 to +550 Table 2 Cv value travel Plug type/ characteristics / Rated travel (mm) / Rated Cv 0.16 0.25 0.4 0.63 1.0 1.6 2.5 4.0 Contoured type Metal seat Equal percentage (%CC) 14.3 .. .. .. .. .. .. .. Linear (LCC) .. .. .. .. .. .. .. .. Inherent rangeability 20:1 30:1 50:1 Nominal size (inch) 1/2 3/4, 1 1 3 |