Azbil Corporation No. SS2-8113-0220 - 3 - Performance Rated Cv value Refer to Table 2 on page 4. Flow characteristics Refer to Figure 1 and 2 on page 4. Inherent rangeability Refer to Table 2. (Rangeability 75 : 1 is available as option for rated Cv larger than 1.0) Allowable differential pressure Refer to Table 3, 4, 5 and 6. Leakage specification . Contoured type plug IEC 60534-4:2006 or JIS B 2005-4:2008 Standard..... Class IV: Leakage less than 0.01% of maximum valve capacity. Option........ Leakage less than 0.001% of maximum valve capacity. . Quick opening plug Leakage less than 0.00001% of maximum valve capacity. Hysteresis error Without positioner: Within 3% F.S. (within 5% F.S.) With positioner: Within 1% F.S. Linearity Without positioner: Within ± 5% F.S. With positioner: Within ± 1% F.S. (VPE : Within ±3% F.S., AVP/HEP : Within ± 2% F.S.) Note) 1)When positioner is not provided, operating performance may vary depending on types of packings used. 2)Parenthesized figures are applicable to Type PSA1 Dimensions Refer to Figure 4, Table 11 and Table 12. Weight Refer to Table 13 and 14. Actuator orientation Refer to Figure 5. Finish Blue (Munsell 10B5/10) or silver, or other specified colors. Note) “ ” shows standard combination of valve body and trim materials. Table 1 Body/trim material combinations and operating temperature ranges (°C) Body material Trim material JIS SCPH2 SCS13A SCS14A ASTM A216WCB A351CF8 A351CF8M JIS SUS304 0 to 300 0 to 300 JIS SUS316 0 to 300 0 to 300 0 to 300 JIS SUS304L 0 to 300 JIS SUS316L 0 to 300 0 to 300 JIS SUS329J1 0 to 300 JIS SUS304 Stellite 0 to 425 0 to 550 JIS SUS304 Stellite face 0 to 425 0 to 550 JIS SUS 316 Stellite face 0 to 425 0 to 550 0 to 550 JIS SUS316 Stellite 0 to 425 0 to 550 0 to 550 JIS SUS304L Stellite 0 to 550 JIS SUS316 Stellite 0 to 450 0 to 450 JIS SUS329J1 Stellite 0 to 550 1 4