Azbil Corporation No. SS2-8113-0300 - 3 - Leakage specification . Contoured type plug IEC 60534-4:2006 or JIS B 2005-4:2008 Standard..... Class IV: Leakage less than 0.01% of maximum valve capacity. Option........ Leakage less than 0.001% of maximum valve capacity. Class VI: Leakage less than 0.00001% of maximum valve capacity. . Quick-opening type plug Leakage less than 0.00001% of maximum valve capacity. Hysteresis error Without positioner: Within 3% F.S. (Within 5% F.S.) ((Within 9% F.S.)) With positioner: Within 1% F.S. ((Within 2% F.S.)) Linearity Without positioner: Within ±5% F.S. ((± 9% F.S.) With positioner: Within ±1% F.S. ((±2% F.S.)) (VPE : Within ±3% F.S., AVP/HEP : Within ±2% F.S.) Note) 1) When positioner is not provided, operating performance may vary depending on type of packings used. 2) Parenthesized figures are applicable to Type PSA1. 3) Double parenthesized figures are applicable to type PSA6/7R. Dimensions Refer to Figure 7 , Table 23 and Table 24. Weight Refer to Table 25. Actuator orientation Refer to Figure 7. Finish Blue (Munsell 10B5/10) or silver, or other specified colors. Table 1 Body / trim material combinations and operating temperature ranges (°C) Body material Trim material JIS SCPH2 SCPH21 SCPH61 SCPL1 SCS11 SCS13A SCS14A SCS16A SCS19A ASTM A216WCB A217WC6 A217C5 A352LCB A351CF8 A351CF8M A351CF3M A351F3 JIS SUS304 -5 to +300 -45 to +300 -196 to +300 JIS SUS316 -5 to +300 -45 to +300 -196 to +300 -196 to +300 JIS SUS304L -45 to +300 -196 to +300 -196 to +300 JIS SUS316L -5 to +300 -45 to +300 -196 to +300 -196 to +300 -196 to 300 -196 to +300 JIS SUS440C -5 to +425 -5 to +425 -5 to +425 JIS SUS329J1 -50 to +300 -196 to +300 JIS SUS304 Stellite -5 to +425 -5 to +550 -5 to 566 -45 to +350 -196 to +550 JIS SUS304 Stellite face -5 to +425 -5 to +550 -5 to +566 -45 to +350 -196 to +550 JIS SUS316 Stellite -5 to +425 -5 to +550 -5 to +566 -45 to +350 -196 to +550 -196 to +550 JIS SUS316 Stellite face -5 to +425 -5 to +550 -5 to +566 -45 to +350 -196 to +550 -196 to +550 JIS SUS304L Stellite -45 to +350 -196 to +550 -196 to +450 JIS SUS316L Stellite -45 to +350 -196 to +450 -196 to +450 -196 to +450 -196 to +450 JIS SUS329J1 Stellite -50 to +550 -196 to +550 JIS SUS304 Soft seat -5 to +230 -45 to +230 -80 to +230 JIS SUS316 Soft seat -5 to +230 -45 to +230 -80 to +230 -80 to +230 JIS SUS316L Soft seat -45 to +230 -80 to +230 -80 to +230 -80 to +230 -80 to +230 JIS SUS329J1 Soft seat -50 to +230 -80 to +230 Note) Column bordered with solid line(" ”), denote values applicable to standard body/trim combination. 1 5