【DO!BOOK・ページリンク】 cv-01 7 / 168 10秒後にBOOKのページに移動します |
|
No. SS2-AGV200-0001 Azbil Corporation - 4 - 3-1-9 Gasket Table 6 Models of AGVB and AGVM *2 Grease provided by lubricator Table 5 Selection of gasket Super-low temperature / Oil-free (Liquid O2.N2) General / Low temp. High temperature Oil-free treatment Between bonnet and body Spiral-shaped gasket Hoop material: SUS316 Filler material: PTFE Metal gasket (PTFE coating) V543(PTFE) Metal gasketV543 Metal gasket (PTFE coating) V543 (PTFE) Between seat ring and body Metal gasket Not necessary Metal gasketV564 (Monel) Metal gasket (PTFE coating) V563 (PTFE) Nominal size inches (mm) 1 (25) 3/4 (20) 1. (40) 2(50) 2.(65) 3(80) 4(100) 1/2 (15) Port size (inches) 0.1 0.16 0.25 0.4 0.63 1.0 1.6 2.5 4.0 8.0 6.3 10 14 1 1. 1. 1. 1. 2 1. 2 2. 2 2. 3 2. 3 4 Rated Cv value 14 21 30 21 30 50 30 50 85 50 85 115 85 115 200 Rated travel (mm) 20 20 20 38 38 38 Flow characteristics Fig.4 Fig. 5 Fig. 6, 7 Figure 4 Cv values 0.1, 0.16, and 0.25 (linear model) Figure 5 Cv values 0.4 to 14 (equal percentage model) Figure 6 Port size 1 to 4 inches (equal percentage model) Figure 7 Cv values 0.4~14 (linear model) Figure 8 Port size 1. to 4 inches (linear model) Scope of control generally considered feasible. (*Cv value in percentage and travel in percentage.) 0 20 40 60 80 0 20 40 60 80 100 100 Cv Value (%) Travel (%) Cv Value (%) Travel (%) 0 20 40 60 80 100 100 50 20 10 5 2 Cv Value (%) Travel (%) 0 20 40 60 80 100 100 50 20 10 5 2 Cv Value (%) Travel (%) 0 20 40 60 80 100 20 40 60 80 100 0 Cv Value (%) Travel (%) 0 20 40 60 80 0 20 40 60 80 100 100 |