Azbil Corporation No. SS2-8113-0310 - 3 - Leakage specifications . Contoured type plug IEC 60534-4:2006 or JIS B 2005-4:2008 . Standard Class IV: Leakage less than 0.01% of maximum valve capacity. . Option Leakage less than 0.001% of maximum valve capacity. Hysteresis error Without positioner: Within 3% F.S. (Within 5% F.S.) ((Within 9% F.S.)) With positioner : Within 1% F.S. ((Within 2% F.S.)) Linearity Without positioner: Within ± 5% F.S. ((Within +9% F.S.)) With positioner: Within ±1% F.S. ((Within +2% F.S.)) (VPE: Within ± 3%, AVP/HEP: Within ± 2% F.S.) Note) 1) When positioner is nor provided, operating performance may vary depending on types of packings used. 2) Parenthesized figures are applicable to Type PSA1. 3) Double parenthesized figures are applicable to type PSA6R. Dimensions Refer to Figure 3, Table 17 and Table 18. Weight Refer to Table 20. Actuator orientation Refer to Figure 4. Finish Blue (Munsell color 10B5/10) or silver, or other specified colors. Note) 1)“ ” shows standard combination of valve body and trim materials. 2) SUS440C is recommended for valves for cavitation/ flushing service of water or for superheated service of water higher than 100oC. Table 1 Body / trim metal combinations and operating temperature ranges (°C) Body material Trim material JIS SCPH2 SCPH21 SCPH61 SCS11 SCS13A SCS14A SCS16A SCS19A ASTM A216WCB A217WC6 A217C5 - A351CF8 A351CF8 M A351CF3 M A351CF3 JIS SUS440C -5 to 425 -5 to 425 -5 to 425 - - - - - JIS SUS304 Stellite -5 to 425 -5 to 550 -5 to 566 - -196 to 550 - - - JIS SUS304 Stellite face -5 to 425 -5 to 550 -5 to 566 - -196 to 550 - - - JIS SUS316 Stellite -5 to 425 -5 to 550 -5 to 566 - -196 to 550 -196 to 550 - - JIS SUS316 Stellite face -5 to 425 -5 to 550 -5 to 566 - -196 to 550 -196 to 550 - - JIS SUS304L Stellite - - - - -196 to 550 - - -196 to 450 JIS SUS316L Stellite - - - - -196 to 450 -196 to 450 -196 to 450 -196 to 450 JIS SUS329J1 Stellite - - - -50 to 550 - -196 to 550 - - Table 2 Cv value and travel Nominal size (inches) 1. 3 2. 3 4 6 8 Port size (Cv value or inches) Cv= 4.0 Cv= 6.3 1 Cv= 6.3 1 1 . 1 1 .1 .1 . 1 . 2 1 . 2 2 .2 . 3 4 3 4 5 Rated Cv value 4.0 6.3 12 6.3 12 21 12 21 30 21 30 50 30 50 85 85 125 200 125 200 310 Rated travel (mm) 25 38 50 75 1 6 |