【DO!BOOK・ページリンク】 cv-02 128 / 132 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-D1M100-0100 Hysteresis error Without positioner: Within 5% F.S. With positioner: Within 1% F.S. Linearity Without positioner: Within ±5% F.S. With positioner: Within ±1% F.S. Dimensions Refer to Figure 1, Table 2 and Table 3 Weight Contact your Azbil sales office Actuator orientation Refer to Figure 2 Finish Blue (Munsell 10B5/10) or silver, or other specified colors. Cv value and flow characteristics Table 1. CV Value Nominal size Port size Cv value inch mm inch mm 1-1/2 40 1-1/2 40 27 1-1/4 32 20 1 25 13 2 50 2 50 45 1-1/2 40 30 1-1/4 32 20 2-1/2 65 2-1/2 65 72 2 50 50 1-1/2 40 30 3 80 3 80 100 2-1/2 65 80 2 50 50 4 100 4 100 180 3 80 100 2-1/2 65 80 6 150 6 150 360 5 125 300 4 100 200 8 200 8 200 580 6 150 400 5 125 300 10 250 10 250 900 8 200 640 6 150 400 12 300 12 300 1200 10 250 1000 8 200 640 14 350 14 350 1620 12 300 1350 10 250 1000 16 400 16 400 2100 14 350 1800 12 300 1350 18 450 18 450 2750 16 400 2350 20 500 20 500 3100 18 450 2950 22 550 22 550 4100 20 500 3100 24 600 24 600 4950 22 550 3500 28 700 28 700 6300 26 650 5625 30 750 30 750 7380 28 700 6300 32 800 32 800 9000 30 750 6300 36 900 36 900 10000 34 850 9500 3 2 14 |