【DO!BOOK・ページリンク】 cv-02 14 / 132 10秒後にBOOKのページに移動します |
|
- 1 - 6th edition No. SS2-ACP110-0100 OVERVIEW The model ACP pressure-balanced cage type control valves are designed for heavy duty service. The valve plug employs a pressure balance function to control high differential pressure fluid with small actuator force. The ACP realizes seat leakage performance as single seat valve by seal-ring structure. In addition, the ACP is equipped the cage plug with a scraper ring to prevent a malfunction caused by foreign object enter between the cage plug and the cage. The actuator is adopted a compact and powerful diaphragm motor. The ACP is widely applicable for reliable control of high or low temperature, high differential pressure process lines where dynamic stability, dynamic stability, low noise, anti-cavitation/flashing are required. SPECIFICATIONS Body Type Straight-through, cast globe valve Nominal size 1., 2, 2., 3, 4, 5, 6, 8 inches Pressure rating . JIS 10K, 16K, 20K, 30K, 40K . ANSI Class 125, 150, 300, 600 . JPI Class 125, 150, 300, 600 End connection . Flanged end; . Welded end; SW (1., 2 inches), BW (2. to 8 inches) Material For body/trim material combinations and operating temperature ranges, refer to Table 1 and 4. Bonnet . Plain bonnet (-17 to 230°C) . Extension bonnet Type 1 (-45 to -17°C and 230 to 400°C) . Extension bonnet Type 2 Connection type Pressure rating Applicable standard FF JIS10K JIS B2210-1984 ANSI Class 125 ANSI B16.5-1981 JPI Class 125 JPI-7S-15-1993 RF JIS10K, 16K, 20K, 30K, 40K JIS B2210-1984 ANSI Class 150, 300, 600 ANSI B16.5-1981 JPI Class150, 300, 600 JPI-7S-15-1993 RJ, LG ANSI Class 150, 300, 600 ANSI B16.5-1981 JPI Class 150, 300, 600 JPI-7S-15-1993 Tongue and groove(groove) Male and female(female) JIS16K, 20K, 30K, 40K JIS B2202-1984 Integral cast type (-100 to -45°C) Welded type (-196 to -100°C) Note) Take care not to exceed the operating temperature ranges specified for respective materials. Gland type Bolted gland Packing / Grease . Grease not provided When V shaped PTFE* packing or PTFE* yarn packing is used. . Grease provided When graphite packing is used. Note) PTFE: Polytetrafluoroethylene Gasket General / Low temp. High temperature Oil free treatment Between body and bonnet Serrated gasket V543 Serrated gasket V543 Serrated gasket (PTFE coating) V543 (PTFE) For upper cage Serrated gasket V543 Serrated gasket V543 Serrated gasket (PTFE coating) V543 (PTFE) For bottom cage Spiral wound gasket V8590 Not necessary Spiral wound gasket V7590 CV3000 Series Pressure-Balanced Cage type Control Valve Model ACP 2 2 Specifications are subject to change without notice. “This product is designed for general industrial use.” |