No. SS2-8113-1200 Azbil Corporation - 12 - Table 12 Air-to-open Note) 1) " " shows a model with standard actuator. 2) Positioner is employed in general. 3) Allowable differential pressure at valve-close in the above table is under the condition of ..P P1 (P2 0). Allowable differential pressure at full closure varies depending on the outlet pressure (P2). Detailed information is avail able on request. 4) Take care not to cause the maximum allowable differential pressure to exceed the maximum operating pressure designated by ANSI B16. 34-1981 or JIS B2201-1984. 5) Take care not to cause the inlet pressure (P1) to exceed allowable differential pressure at full closure. 6) The upper figures denote the operating allowable differential pressure. The lower denote the allowable differential pressure at full closure. Rating Actuator model No. Supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Differential pressure (by nominal size(inches)) kPa {kgf/cm2} 1 . 2 3 4 6 8 JIS63K ANSI 900, 1500 JPI 900, 1500 HA3R 270 {2.8} 80 to 240 {0.8 to 2.4} 15000 {153} 11400 {116} 7650 {78.0} 5690 {58.0} 25900 {264} 18600 {190} 11100 {113} 7260 {74.0} 290 {3.0} 18600 {190} 17200 {175} 11100 {113} 7260 25900 {74.0} {264} 18600 {190} 340 {3.5} 22800 {233} 25900 {264} HA4R 270 {2.8} 80 to 240 {0.8 to 2.4} 20700 {211} 19700 {201} 13200 {135} 9900 {110} 6570 {67.0} 4900 {50.0} 25900 {264} 25900 {264} 22300 {227} 15600 {159} 8920 {91.0} 5590 {57.0} 290 {3.0} 20600 {210} 19900 {203} 14900 {152} 8920 {91.0} 5590 {57.0} 25900 {264} 22300 {227} 15600 {159} 8920 {91.0} 5590 {57.0} 340 {3.5} 20600 {210} 15600 {159} 22300 {227} 15600 {159} VA5R 270 {2.8} 40 to 200 {0.4 to 2.0} 13500 {138} 9020 {92.0} 6770 {69.0} 22900 {234} 13800 {141} 9320 {950} PSA6R 400 {4.0} 200 to 340 {2.0 to 3.5} 25900 {264} 500 {5.1} 200 to 390 {2.0 to 4.0} 18700 {191} 25900 {264} ANSI 2500 JPI 2500 HA3R 270 {2.8} 80 to 240 {0.8 to 2.4} 15000 {153} 11400 {116} 10400 {106} 6960 {71.0} 4310 {44.0} 25900 {264} 18600 {190} 16600 {169} 9710 {99.0} 4410 {45.0} 290 {3.0} 18600 {190} 17200 {175} 15600 {159} 9710 {99.0} 4310 {44.0} 25900 {264} 18600 {190} 16600 {169} 4410 {45.0} 340 {3.5} 18500 {189} 16600 18600 {169} {190} HA4R 270 {2.8} 80 to 240 {0.8 to 2.4} 20700 {211} 19700 {201} 18500 {189} 12100 {123} 7450 {76.0} 6570 {67.0} 43100 {440} 35200 {359} 31800 {324} 19900 {203} 10800 {110} 8920 {91.0} 290 {3.0} 20600 {210} 20600 {210} 1800 {184} 10800 {110} 8920 35200 {91.0} {359} 31800 {324} 19900 {203} 340 {3.5} 19900 {203} VA5R 270 {2.8} 80 to 240 {0.4 to 2.0} 24.1 {246} 43.1 {440} PSA6R 390 {4.0} 200 to 340 {2.0 to 3.5} 35500 {362} 43100 {440} 490 {5.0} 200 to 390 {2.0 to 4.0} 21200 {216} 36100 {368} |