No. SS2-ADV100-0100 Azbil Corporation - 2 - 2. Basic Model Numbers The basic model number of the CV3000 Alphaplus series of control valves you eventually choose will be either: Model ADVB: JIS 10K, ANSI 150, JPI 150 Model ADVM: JIS 20K, JIS 30K, ANSI 300, JPI 300 3. Optional Specifications 3-1 Body 3-1-1 Port diameter and flow control characteristics The selection of the port diameter and the rated Cv value falls within the scope of Table 1 according to the flange diameter. Note) *: In case of linear characteristics, it is changed a characteristics by positioner. Note) : Scope of control generally considered feasible (Cv value in percentage and travel in percentage and input signal.) 3-1-2 End connection standard (flange type) We manufacture the following flange type products. JIS 10K, 20K, 30K (JIS B2210-1984) ANSI 150, 300 (ASME/ANSI B16.5-1988 JPI 150, 300 (JPI-75-15-1993) 3-1-3 Bonnet We manufacture bonnets that can be used at fluid temperatures ranging from -17°C to+ 400°C. Plain type : -5°C < t < +230°C (Stainless steel: ASTM A351CF8, A351CF8M is -17°C < t < +230°C) Extension type : +230°C < t < +400°C (High temperature), -45°C < t < -17°C (Low temperature: Stainless steel) Table 1 Nominal size and port diameter Figure 2 Equal percentage Figure 3 Linear Nominal size (inches) 6 8 10 12 Port diameter (inches) 4 6 6 8 6 8 10 8 10 12 Rated Cv value 215 450 450 705 450 705 1100 705 1100 1580 Rated travel (mm) 38 75 Flow characteristics Equal percentage, linear* 100 50 20 10 5 2 0 20 40 60 80 100 Cv value (%) Travel (%) 100 80 60 40 20 0 20 40 60 80 100 Cv value (%) Travel (%) |