【DO!BOOK・ページリンク】 cv-02 84 / 132 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-ADV100-0100 - 7 - Allowable differential pressures for model ADVM Note) 1. Note that the maximum allowable differential pressures must not exceed the maximum working pressure specified by JIS B2201-1984, ANSI B 16.34-1981, and JPI-7S-65-83. 2. In the differential pressure column, upper figures show operating differential pressures and lower figures show differential pressures when the valve is fully closed. Table 8 Air-to-open Nominal size (inches) Actuator Supply kPa{kgf/cm2} Spring range kPa{kgf/cm2} Differential pressure (classified by port diameter) kPa {kgf/cm2} 4 6 8 10 12 6 PSA3R 390 {4.0} 80 to 240 {0.8 to 2.4} 1800 {18.0} 1800 {18.0) - - - 5100 {52.0} 5100 {52.0} - - - PSA4R 390 {4.0} 80 to 240 {0.8 to 2.4} 2900 {30.0} 2900 {30.0} - - - 5100 {52.0} 5100 {52.0} - - - 8 HA4R 390 {4.0} 80 to 240 {0.8 to 2.4} - 2900 {30.0} 2900 {30.0} - - - 5100 {52.0} 5100 {52.0} - - 10 HA4R 390 {4.0} 80 to 240 {0.8 to 2.4} - 2000 {20.4} 2000 {20.4} 2000 {20.4} - - 4400 {45.0} 4400 {45.0} 4400 {45.0} - 12 HA4R 390 {4.0} 80 to 240 {0.8 to 2.4} - - 500 {5.0} 500 {5.0} 500 {5.0} - - 2000 {20.4} 2000 {20.4} 2000 {20.4} Table 9 Air-to-close Nominal size (inch) Actuator Supply kPa{kgf/cm2} Spring range kPa{kgf/cm2} Differential pressure (classified by port diameter) kPa {kgf/cm2} 4 6 8 10 12 6 PSA3D 390{4.0} 80 to 240 {0.8 to 2.4} 1800 {18.0} 1800 {18.0} - - - 5100 {52.0} 5100 {52.0} - - - PSA4D 390{4.0} 80 to 240 {0.8 to 2.4} 2900 {30.0} 2900 {30.0} - - - 5100 {52.0} 5100 {52.0} - - - 8 HA4D 390{4.0} 80 to 240 {0.8 to 2.4} - 1500 {15.3} 1500 {15.3} - - - 5100 {52.0} 5100 {52.0} - - 10 HA4D 390{4.0} 80 to 240 {0.8 to 2.4} - 1500 {15.3} 1500 {15.3} 1500 {15.3} - - 5100 {52.0} 5100 {52.0} 5100 {52.0} - 12 HA4D 390{4.0} 80 to 240 {0.8 to 2.4} - - 500 {5.0} 500 {5.0} 500 {5.0} - - 4400 {45.0} 4400 {45.0} 4400 {45.0} 2 8 |