- 1 - 6th edition No. SS2-8113-2600 Venturi Throat Type Angle Control Valves Model HAV OVERVIEW Model HAV venturi throat type angle control valves are compact, high-performance control valves designed for heavyduty service. The valve plug is highly vibration-resistant as it is held by a top guide section which has a large sliding area. The flow shut-off performance complies with the IEC/JIS Standards. The acturator, integrated with simplest mechanisms, utilizes a compact yet powerful diaphragm actuator loaded with multiple springs. SPECIFICATIONS Body Type Cast angle valve Nominal size 1, 1., 2, 2., 3, 4, 5, 6 inches Pressure rating . JIS 10K, 16K, 20K, 30K, 40K . ANSI Class 125, 150, 300, 600 . JPI Class 125, 150, 300, 600 End connection Flanged end: Material For body/trim material combinations and operating temperature ranges, refer to Table 1. Flanged end Pressure rating Standard FF JIS 10K JIS B2212-1972 ANSI Class 125 ANSI B16.5-1968 JPI Class 125 JPI-7S-15-1993 RF JIS10K JIS B2212-1972 JIS16K JIS B2213-1967 JIS20K JIS B2214-1967 JIS30K JIS B2215-1967 JIS40K JIS B2216-1967 ANSI Class 150, 300, 600 ANSI B16.5-1968 JPI Class 150, 300, 600 JPI-7S-15-1993 RJ, LG ANSI Class 150, 300, 600 ANSI B16.5-1968 JPI Class 150, 300, 600 JPI-7S-15-1993 Bonnet . Plain bonnet (0 to 200 °C) . Extension bonnet (-50 to 0°C and 200 to 425°C) . Bellows type (for operating temperature and pressure range, refer to Figure.2) Note) take care not to exceed the operating temperature ranges specified for respective materials. Gland type Bolted gland Packing/Grease . Grease not provided When V shaped PTFE packing or PTFE yarn packing is used. . Grease provided When graphite packing is used. Note) PTFE: Polytetrafluoroethylene Gasket Type Flat type, serrated type Material Carbon steel (S15C), stainless steel (SUS316,SUS316L, SUS329J1), copper, aluminum 3 1 Specifications are subject to change without notice. “This product is designed for general industrial use.” |