【DO!BOOK・ページリンク】 cv-06 10 / 48 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-AGV200-0300 - 7 - 3-2 Actuator 3-2-1 Actuator and valve actions Table 5 Specification of actuator Note) *: The travel transmission is a standard specification for the proportional control, but that is a optional spcification for the two position control. Valve action The valve action is decided by selecting the operation of the actuator action. Signal to open: actuator action where the valve opens as the input signal increases Signal to close: actuator action where the valve closes as the input signal increases 3-2-2 Tables of allowable differential pressures Ensure the required shut-off differential pressure specified in the equipment design is satisfied by selecting an actuator with an allowable differential pressure equal to or higher than the shut-off pressure, according to the seat leakage class. Seat leakage, Class IV (0.01% of rated Cv value) . Model AGVB: Table 6-1 and 6-2 on page 8 . Model AGVM: Table 6-3 and 6-4 on page 8 Seat leakage, Class VI (high shutoff model: soft seat) . Model AGVB: Table 7-1 and 7-2 on page 8 . Model AGVM: Table 7-3 and 7-4 on page 8 3-2-3 Finish The normal standard coating color for Azbil Corporation's control valves is blue (Munsell 10B 5/10). Silver is also available as standard. Standard colors are also used for such optional accessories as positioners, pressure regulator with filter, and solenoid valves. 4. Fluid Conditions It is important to make the fluid conditions clear in selecting the control valve. Please fill in each data on “Fluid specifications” column in the lower of the model selection table. Calculation of the Cv values and expected noise For calculation of the Cv values and expected noise, refer to following document. Selecting the control valves: No. IB2-8000-0100 Azbil Corporation has developed personal computer software to calculate Cv values and expected noise. Please specify if you require such a PC-based tool. Type Electronic motor Control action Proportional control or two-position control Power supply Single phase 100V, 110V, 115V, 120V, 200V, 210V, 220V, 230V, 240V AC ±10%, 50/60 Hz) Input signal 4 to 20 mA DC, 1 to 5 VDC Open or close contact input Action Direct or reverse Power failure action Close, open or hold Input resistance 250 .. Power supply capacity (general) 0.32A (power supply 100V AC) 0.18A (power supply 200V AC) Insulation resistance Between input terminal and case 100 M..../ 500V DC With stand voltage Between poser supply terminal and case 500V / 1 min Main material Case: Aluminium die-casting (ADC 12) Stem: SUS303 Yoke: Carbon steel (SCPH2) Type of protection IP65 equivalent Explosion-proof None Motor Reversible motor Coil insulation class E Rated temperature Continuity (built-in thermal switch: 120°C trip automatic operation type) Position sensor Potentiometer Protective device Built-in open/close limit switch (standard) Built-in lower torque limiter (standard) Electrical connection G1/2 (two position) Ambient temperature limits -25 to 55°C Ambient humidity limits 10 to 90%RH Vibration tolerance 2 G 5 to 100 Hz Travel transmission* 1to 5V DC Manual operation Top handle (standard) Dead band Within ±1% F.S. Operation speed (open .. close) 16 sec. . With the Alphaplus, the valve closes as the plug lowers. The valve action depends, in turn, on whether an signal to close or signal to open actuator is chosen. . When the power supply is “Stop”, the actuator keeps the travel transmission of that time. You can specify any other color using the number code of the Japan Paint Industry Assignment or the Munsell color system. Mark Name Description - Fluid name Name or symbol of fluid to flow through control valve Q Flow rate Maximum (MAX), normal (NOR), and minimum (MIN) flow rates to be controlled P1 Upstream pressure Pressure on upstream side of control valve P2 Downstream pressure Pressure on downstream side of control valv ..P Differential pressure Pressure loss at control valv ..P close Differential pressure when fully closed Differential pressure when the valve is fully closed (actuator selection condition) Temp Temperature Temperature of fluid on upstream side G Specific gravity Specific gravity of the fluid V Viscosity Viscosity at the temperature of the fluid on upstream side - Flashing % Weight percentage of flashing to occur on downstream side when pressure is reduced by the control valve ΔP Q P1 P2 6 1 |