No. SS2-AGV200-0300 Azbil Corporation - 8 - Valve seat leakage, Class IV: 0.01% of the rated Cv value Table 6-1 Model AGVB nominal size 1/2, 3/4, and 1 inch Note that the allowable differential pressure varies with the rated Cv value you have selected. Note) Note that the maximum allowable differential pressures must not exceed the maximum working pressures specified by JISB2201-1984, ANSIB16.34-1981, and JPI-7S-65-83. Table 6-2 Model AGVB nominal size 1., 2 inches Note that the allowable differential pressure varies with the port diameter (inches) you have selected. Note) Note that the maximum allowable differential pressures must not exceed the maximum working pressures specified by JISB220-1-1984, ANSIB16.34-1981, and JPI-7S-65-83 Table 6-3 Model AGVM nominal size 1/2, 3/4, and 1 inch Note that the allowable differential pressure varies with the rated Cv value you have selected. Note) 1. Note that the maximum allowable differential pressures must not exceed the maximum working pressures specified by JISB2201-1984, ANSIB16.34-1981, and JPI-7S-65-83. Note) 2. In the differential pressure column, upper figures show normal differential pressures and lower figures differential pressures when the valve is fully closed. At your request, we can manufacture control valves with normal pressures exceeding 1960 kPa. Table 6-4 Model AGVM nominal size 1., 2 inches Note that the allowable differential pressure varies with the port diameter (inches) you have selected. Note) 1. Note that the maximum allowable differential pressures must not exceed the maximum working pressures specified by JISB2201-1984, ANSIB16.34-1981, and JPI-7S-65-83. Note) 2. In the differential pressure column, upper figures show normal differential pressures and lower figures differential pressures when the valve is fully closed. At your request, we can manufacture control valves with normal pressures exceeding 1960 kPa. Valve seat leakage, Class VI: high shutoff model: soft seat Table 7-1 Model AGVB nominal size 1/2, 3/4, and 1 inch Note that the allowable differential pressure varies with the rated Cv value you have selected. Note) Note that the maximum allowable differential pressures must not exceed the maximum working pressures specified by JISB220-1-1984, ANSIB16.34-1981, and JPI-7S-65-83. Table 7-2 Model AGVB nominal size 1., 2 inches Note that the allowable differential pressure varies with the port diameter (inches) you have selected. Note) Note that the maximum allowable differential pressures must not exceed the maximum working pressure specified by JISB220-1-1984, ANSIB16.34-1981, and JPI-7S-65-83. Table 7-3 Model AGVM nominal size 1/2, 3/4, and 1 inch Note that the allowable differential pressure varies with the rated Cv value you have selected. Note) 1. Note that the maximum allowable differential pressures must not exceed the maximum working pressures specified by JISB220-1-1984, ANSIB16.34-1981,and JPI- 7S-65-83. Note) 2. In the differential pressure column, upper figures show normal differential pressures and lower figures differential pressures when the valve is fully closed. At your request, we can manufacture control valves with normal pressures exceeding 1960 kPa. Table 7-4 Model AGVM nominal size 1., 2 inches Note that the allowable differential pressure varies with the port diameter (inches) you have selected. Note) 1. Note that the maximum allowable differential pressures must not exceed the maximum working pressures specified by JISB220-1-1984, ANSIB16.34-1981, and JPI-7S-65-83. Note) 2. In the differential pressure column, upper figures show normal differential pressures and lower figures differential pressures when the valve is fully closed. At your request, we can manufacture control valves with normal pressures exceeding 1960 kPa. Nominal size [inches] Actuator Differential pressure (by Cv value) kPa {kgf/cm2} 0.25 or less 0.4 0.63 1.0 1.6 2.5 4.0 6.3 8.0 10 14 1 inch or less EA1 1960{20.0} Nominal size inches Actuator Differential pressure (by Port size) kPa {kgf/cm2} 1 1. 1. 2 1. EA1 1960 {20.0} 1870 {19.0} 1270 {12.9} - 2 - 760 {7.7} Nominal size inches Actuator Differential pressure (by Cv value) kPa{kgf/cm2} 0.25 or less 0.4 0.63 1.0 1.6 2.5 4.0 6.3 8.0 10 14 1/2 3/4 1 EA1 1960{20.0} 5100{52.0} 4120{42.0} 3040{31.0} Nominal size inches Actuator Differential pressure (by Port size) kPa{kgf/cm2} 1 1. 1. 2 1. EA1 1960 {20.0} 1870 {19.0} 1270 {12.9} - 3040 {31.0} 2 - 760 {7.7} Nominal size inches Actuator Differential pressure (by Cv value) kPa{kgf/cm2} 0.25 or less 0.4 0.63 1.0 1.6 2.5 4.0 6.3 8.0 10 14 1 inch or less EA1 1960{20.0} Nominal size inches Actuator Differential pressure (by port size) kPa{kgf/cm2} 1 1. 1. 2 1. PSA1R 1700{17.3} 1100 {11.2} 630 {6.4} - 2 - 250 {2.5} Nominal size inches Actuator Differential pressure (by Cv value) kPa{kgf/cm2} 0.25 or less 0.4 0.63 1.0 1.6 2.5 4.0 6.3 8.0 10 14 1/2 3/4 1 EA1 1960{20.0} 1700{17.3} 2940{30.0} 2070{21.1} Nominal size inches Actuator Differential pressure (by port size) kPa{kgf/cm2} 1 1. 1. 2 1. PSA1R 1700 {17.3} 1100 {11.2} 630 {6.4} - 2 - 250 {2.5} |