【DO!BOOK・ページリンク】 cv-06 17 / 48 10秒後にBOOKのページに移動します |
|
No. SS2-8114-0200 Azbil Corporation - 4 - Note) 1) “ ” shows standard combination of valve body and trim materials. Note) “ ” denotes production range. Table 1 Body/trim material combinations and operating temperature ranges (°C) Body material Trim material JIS FC200 SCPH2 SCPH21 SCPH61 SCPL1 SCS11 SCS13A SCS14A SCS16A SCS19A ASTM A126Gr.A A216WCB A217WC6 A217C5 A352LCB - A351CF8 A351CF8M A351CF3M A351CF3 JIS SCS304 0 to +200 -5 to +300 - - -45 to +300 - -196 to +300 - - JIS SUS316 0 to +200 -5 to +300 - - -45 to +300 - -196 to +300 -196 to +300 - JIS SUS304L - - - - -45 to +300 - -196 to +300 - - JIS SUS316L - - - - -45 to +300 - -196 to +300 -196 to +300 -196 to +300 JIS SUS440C -5 to +425 -5 to +425 -5 to +425 - - - - - JIS SUS329J - - - - - -50 to +300 - -196 to +300 - - JIS SUS304 Stellite - -5 to +425 -5 to +550 -5 to +556 -45 to +350 - -196 to +550 - - JIS SUS304 Stellite face - -5 to +425 -5 to +550 -5 to +556 -45 to +350 - -196 to +550 - - JIS SUS316 Stellite - -5 to +425 -5 to +550 -5 to +556 -45 to +350 - -196 to +550 -196 to +550 - JIS SUS316 Stellite face - -5 to +425 -5 to +550 -5 to +556 -45 to +350 - -196 to +550 -196 to +550 - JIS SUS304L Stellite - - - - -45 to +350 - -196 to +550 - - JIS SUS316L Stellite - - - - -45 to +350 - -196 to +450 -196 to +450 -196 to +450 JIS SUS329J1 Stellite - - - - - -50 to +550 - -196 to +550 - - JIS SUS304 Soft seat 0 to +230 -5 to +230 - - -45 to +230 - -80 to +230 - - JIS SUS316 Soft seat -0 to +230 -5 to +230 - - -45 to +230 - -80 to +230 -80 to +230 - JIS SUS316L Soft seat - - - - -45 to +230 - -80 to +230 -80 to +230 -80 to +230 JIS SUS329JI Soft seat - - - - - -50 to +230 - -80 to +230 - - Table 2 Body material Trim material JIS SCPH2 SCS13A SCS14A SCS16A SCS19A Titanium ASTM CW-12MW (Hastelloy C equivalent) Alloy 20 ASTM A216WCB A351CF8 A351CF8M A351CF3M A351CF3 - - - JIS Titanium alloy - - - - - -196 to +315 - - JIS Titanium - - - - - -196 to +315 - - JIS ASTM CW-12MW (Hastelloy C equivalent) - - - - - - -196 to +450 - JIS Alloy 20 - - - - - - - -196 to +300 JIS Monel -5 to +300 -196 to +300 -196 to +300 -196 to +300 -196 to +300 - - - Table 3 Cv value and travel Plug type/characteristic/ Rated travel (mm) / Rated Cv value 0.01 0.04 0.1 0.16 0.25 0.4 0.63 1.0 1.6 2.5 4.0 6.3 10 14 Contoured type Metal seat Equal percentage (% CF) 14.3 Linear (LCF) Soft seat Equal percentage (%TF) Linear (LTF) Inherent rangeability 20:1 25:1 20:1 30:1 50:1 End connection (inch) 1/2 3/4 1 |