Azbil Corporation SS2-SSL100-0100 - 3 - .. Specifications Applicable control valves CV3000 Alphaplus series Models: AGVB / AGVM ADVB / ADVM Press. Rating JIS10K / 16K / 20K ANSI Class 150# / Class 300# JPI Class 150# / Class 300# Combined actuator models: PSA1 / PSA2 / PSA3 / PSA4 / HA4 CV3000 Alphaplus series Models: HLS / HLC / HTS / HSC ACP / HCB / ACN / HCN Press. Rating JIS10K / 16K / 20K ANSI Class 150# / Class 300# JPI Class 150# / Class 300# Combined actuator models: PSA1 / HA2 / HA3 / HA4 FloWingTM Eccentric Rotary Control Valve Models: VFR Press. Rating JIS10K / 20K ANSI Class 150# / Class 300# JPI Class 150# / Class 300# Combined actuator models: RSA1 / RSA2 / VR3 . Packing Structure and Materials: Braided with PTFE fibers with a carbon fiber core Packing Name: #P4519 Operating Temperature Range: -17°C to 230°C Maximum Operating Pressure: 5 MPa Grease: Not used for CV3000 Alphaplus and CV3000 series Used for FloWingTM . Live Load Structure: Packing follower pressure application method by using Belleville spring Materials: SUS304 . Leakage performance evaluation Test medium: Helium Test method: Azbil Corporation original (Combined load of mechanical and thermal cycle) Performance: Less than 500 ppm and 100 ppm* at Methane converted level (conforms to ANSI/ISA-93.00.01-100) Measurement method: Complies with U.S.EPA 40 CFR 60 Method 21 *There is a possibility that the temperature range is changed by the combination of actuator. 8 3 |