No. SS2-DST100-0700 Azbil Corporation - 4 - Transmitter handling notes To make the most of the performance this transmitter can offer, please use it properly noting the points mentioned below. Before using it, please read the userfs manual. Transmitter installation notes Wiring notes WARNING . When installing the transmitter, ensure that gaskets do not protrude from connecting points into the process (such as adapter flange connection points and connecting pipes and flanges). Gasket protrusion may result in leaks and output errors. . Do not use the transmitter outside its defined pressure, temperature, and connection specifications. A serious accident may otherwise occur due to damage and leaks. . When performing wiring work in explosion-proof areas, follow the work method specified in the explosion-proof guidelines. In addition, when the wiring for an explosionproof product is a pull-in pressure-resistant packing-cable, be sure to use a pressure-resistant packing-cable adapter certified by Azbil Corporation. . Be sure to use the cable which allowable temperature is more than 65‹C. CAUTION . After installing the transmitter, do not stand on it. Using it as a foothold could cause it to collapse and cause physical injury. . Be careful not to hit the glass indicator with tools etc. This could break the glass and cause injury. . The transmitter is heavy. Wear safety shoes and take care when installing it. WARNING . To avoid shocks, do not perform electrical wiring work with wet hands or with live wires. CAUTION . Do wiring work properly in conformance with the specifications. Wiring mistakes may result in malfunction or irreparable damage to the instrument. . Use a power supply that conforms to the specifications. Use of an improper power supply may result in malfunction or irreparable damage to the instrument. PERFORMANCE SPECIFICATIONS Table 1 Performance specifications DP Measuring span 0.75 to 100 kPa DP setting range -100 < URV < 100 kPa (*1) -100 < LRV < 100 kPa (*2) Note)*1: URV denotes the value for 100% (20 mA) output. *2: LRV denotes the value for 0% (4 mA) output. Design pressure setting range 0.17 to 3.5 MPa abs. Design temperature setting range -100 to 650‹C Calculation equation See Figure 1. Accuracy (output after compensation) Shown are the upper limit (URV) and lower limit (LRV) of the calibration range or the percentage ratio of the maximum value of the span to ƒÔ (kPa.) PPREF.: designed pressure PPMAX.: max. pressure of process Accuracy% = } (0.025 + A + B + C + D + E) (* E: only when the temperature is input.) A: 0.075% .................................................................. 0.075% ~ %................................... B: %...................................................... %.............................. C: 0.075% .................................................................. abs. %.................................................. abs. D: % E: 0.1% (Only when the temperature is input.) Square root output: When output is 50 to 100%; same as that of linear output. When output is 7.1 to 50%; value of linear output ~ % (Not specified for dropout area) When output is 7.1% or below;Not specified x PPREF PPMAX .. ~ ----------------.. (.. ..) . 12.5kPa 12.5 x ---------- PPMAX PPREF ~ ---------------- x PPREF PPMAX .. ~ ----------------.. .. .. . 12.5kPa 0.1 PPMAX 3.5 ~ ---------------- x PPMAX PPREF .. ~ ----------------.. .. .. . 25kPa 0.1 25 x ~ ----- PPMAX PPREF ---------------- PPMAX 3.5 ~ ~ ---------------- x PPMAX PPREF .. ~ ----------------.. .. .. . 25kPa PPREF . 0.35MPa 0.075 0.35 PPREF ~ --------------- PPREF . 0.35MPa 0.15 x PPREF ~ 1000 ~ --------------------------------- 50 Output ------------------ |