No. SS2-PTG300-0100 Azbil Corporation - 6 - Transmitter handling notes To get the most from the performance this transmitter can offer, please use it properly noting the points mentioned below. Before using it, please read the Instruction Manual. Transmitter installation notes Wiring notes Handling precautions for HARTspecification devices . "If you need to operate with a secondary host (HART communicator, etc.), set the communication interval of the primary host (DCS, device management system) to 8 seconds or more, or suspend communication from the primary host. If the primary host repeats HART communication within 8 seconds, the request from the secondary host may not be received (communication may not be possible). . "If electrical noise in the environment prevents HART communications with the host, take countermeasures such as separating the signal cables from the source of the noise, improving the grounding, changing to shielded signal cables, etc. Even if noise interferes with HART communications, the 4-20 mA analog signal will be unaffected and can be used for control. . "If this product is being operated in multidrop mode, there is a limit to the number of devices that can be used. If you are using multidrop mode, please consult with us. WARNING . When installing the transmitter, ensure that gaskets do not protrude from connecting points into the process (such as adapter flange connection points and connecting pipes and flanges). Gasket protrusion may result in leaks and output errors. . Do not use the transmitter outside its defined pressure, temperature, and connection specifications. A serious accident may otherwise occur due to damage and leaks. . When performing wiring work in explosion-proof areas, follow the work method specified in the explosion-proof guidelines. CAUTION . After installing the transmitter, do not stand on it. Using it as a foothold could cause it to collapse and cause physical injury. . Be careful not to hit the glass indicator with tools etc. This could break the glass and cause injury. . The transmitter is heavy. Wear safety shoes and take care when installing it. . Impact to transmitter can damage sensor module. WARNING . To avoid shocks, do not perform electrical wiring work with wet hands or with live wires. CAUTION . Do wiring work properly in conformance with the specifications. Wiring mistakes may result in malfunction or irreparable damage to the instrument. . Use a power supply that conforms to the specifications. Use of an improper power supply may result in malfunction or irreparable damage to the instrument. |