【DO!BOOK・ページリンク】 fi-04 183 / 228 10秒後にBOOKのページに移動します |
|
No. SS2-MVC200-0100 Azbil Corporation - 4 - Damping: Adjustable between 0 and 128 seconds Low flow cutoff Adjustable between 0 and 20% of setting range Power failure An EEPROM retains data record of totalized flow and various set up parameters Function Totalized function Counting by one count according to the display flow unit setting. Auto ranging function After turning on the power or the peak value is reset, the AIRcube automatically sets the measuring range at 80% of the maximum flow rate. Leak check function Calculate the leak rate by measuring line pressure with a built in pressure sensor. Table 3 Factory Default Setting ITEM Factory Default Setting Main display Totalized flow Unit Totalized flow m3 Flow rate Nm3/h Totalized cost cost /h Damping 1 sec Low flow cut 3% of Flow rate range Flow rate range Customer instruction Leak check Pressure setting value 0.65MPa G Tag XXXXXXXX Reference temperature 0°C Reference pressure 101.325 kPa (abs) Pulse weight Customer omstruction Cost rate Customer omstruction Max flow Customer omstruction Language Japanese t1 t2 100% Pressure Normal operation Time Pipe and valve shut. Setting pressure of compressor Compressor stopped. 70% Compressor start. 80% Flow rate = 100 t1 (t1 + t2) |