Azbil Corporation No. SS2-MGG41F-0100 - 5 - Network Parameters The following table shows the key parameter values that affect interoperability of the Fieldbus devices. The LAS needs to be configured to satisfy these parameters. If other devices on the same Fieldbus network require a greater number for them, the greater number must be used. This will degrade network performance, though. Note) . A LAS requires parameters other than those listed here to operate. Please refer to the user's manual that comes with your LAS device. . The T3 needs to be set between 15 seconds and 60 seconds. *1. unit: Octet time (256 s) *2. unit: Slot-Time Factory default setting Note) *3. If a specific Node Address other than 0xF8 is required, specifiy a PD TAG No. Symbol Parameter name Default value Range of Values V(ST) Slot Time *1 5 5 to 100 V(MID) Minimum Interframe Gap *1 10 10 to (V (MRD) -1) × V (ST), smaller than 120 inclusive. V(MRD) Maximum Response Delay *2 4 V (MRD) × (V (ST) shall be greater than 20 and V (MRD) shall be smaller than 11, inclusive. T1 SM Step Timer 48000 (15 seconds) - T2 SM Set Address Sequence Timer 2880000 (90 seconds) T2 > T3 T3 SM Set Address Wait Timer 1440000 (45 seconds) T2 > T3 V(FUN) First Unpolled Node 0x25 0x14 to 0xF7 V(NUN) Number of consecutive Unpolled-Node 0xBA 0x00 to 0xE4 V(MSO) Maximum Scheduling Overhead *1 0x00 0x00 to 0x3F V(DMDT) Default Minimum Token Delegation time *1 0x56 0x20 to 0x7FFF V(DTHT) Default Token Holding Time *1 0x0400 0x0114 to 0xFDE8 (65,000) V(TTRT) Target Token Rotation Time *1 4096 1 to 60000 ms V(LTHT) Link Maintenance Token Holding Time *1 0x0124 0x0124 to 0xFDE8 (65,000) V(TDP) Time Distribution Period 5000 5 to 55000 ms V(MICD) Maximum Inactivity to Claim LAS Delay *1 2000 1 to 4095 V(LDDP) LAS Database Distribution Period 3000 100 to 55000 ms Parameter name Default setting PD TAG No. Specified by a customer or blank Node Address 0xF8 *3 Device Class Basic 4 2 |