No. SS2-VFR100-0100 Azbil Corporation - 6 - Metar Seat, Graphite packing “G6610CH+P6528” (+230 to +350°C) Table 8 Air-to-Close Table 9 Air-to-Open Soft seat, PTFE packing Table 10 Air-to-Close Table 11 Air-to-Open Actuator model No. Air supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Differential pressure [Upper : by nominal size (inch), Lower : port capacity] kPa{kgf/cm2} 6 8 10 12 Full 60% 40% Full 60% 40% Full 60% 40% Full 60% 40% VR3D 340 {3.5} 80 to 160 {0.8 to 1.6} 2060 {21.0} 2060 {21.0} 2060 {21.0} 980 {10.0} 980 {10.0} 980 {10.0} 490 {5.0} 80 to 160 {0.8 to 1.6} 980 {10.0} 980 {10.0} 980 {10.0} 640 {6.5} 640 {6.5} 640 {6.5} VR3HD (high differential press) 340 {3.5} 90 to 160 {0.9 to 1.6} 3300 {33.6} 4600 {46.9} 1600 {16.3} 2200 {22.4} 490 {5.0} 90 to 160 {0.9 to 1.6} 1700 {17.3} 2500 {25.5} 1000 {10.2} 1600 {16.3} Actuator model No. Air supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Differential pressure [Upper : by nominal size (inch), Lower : port capacity] kPa{kgf/cm2} 6 8 10 12 Full 60% 40% Full 60% 40% Full 60% 40% Full 60% 40% VR3R 340 {3.5} 80 to 160 {0.8 to 1.6} 630 {6.4} 630 {6.4} 630 {6.4} 180 to 270 {1.8 to 2.8} 2040 {20.8} 2040 {20.8} 2040 {20.8} 970 {9.9} 970 {9.9} 970 {9.9} 480 {4.9} 480 {4.9} 480 {4.9} 290 {3.0} 290 {3.0} 290 {3.0} VR3HR (high differential press) 340 {3.5} 90 to 160 {0.9 to 1.6} 1200 {12.2} 1700 {17.3} 190 to 270 {1.9 to 2.8} 3500 {35.7} 4800 {48.9} 1700 {17.3} 2400 {24.5} 870 {8.9} 1200 {12.2} 520 {5.3} 830 {8.4} Actuator model No. Air supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Differential pressure [Upper : by nominal size (inch), Lower : port capacity] kPa{kgf/cm2} 6 8 10 12 Full 60% 40% Full 60% 40% Full 60% 40% Full 60% 40% VR3D 340 {3.5} 80 to 160 {0.8 to 1.6} 2060 {21.0} 2060 {21.0} 2060 {21.0} 981 {10.0} 981 {10.0} 981 {10.0} 490 {5.0} 80 to 160 {0.8 to 1.6} 981 {10.0} 981 {10.0} 981 {10.0} 780 {8.0} 780 {8.0} 780 {8.0} Actuator model No. Air supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Differential pressure [Upper : by nominal size (inch), Lower : port capacity] kPa{kgf/cm2} 6 8 10 12 Full 60% 40% Full 60% 40% Full 60% 40% Full 60% 40% VR3R 340 {3.5} 80 to 160 {0.8 to 1.6} 1180 {12.0} 1180 {12.0} 1180 {12.0} 180 to 270 {1.8 to 2.8} 2060 {21.0} 2060 {21.0} 2060 {21.0} 981 {10.0} 981 {10.0} 981 {10.0} 490 {5.0} 490 {5.0} 490 {5.0} 340 {3.5} 340 {3.5} 340 {3.5} |