【DO!BOOK・ページリンク】 cv-04 30 / 68 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-VFR100-0100 - 9 - Note) *1. The H dimensions enclosed in the parentheses are for the spring range 80 to 160 kPa {0.8 to 1.6 kgf/cm2}. *2. Face-to-face dimensions of the anti-cavitation specification (built-in type) will not be changed. Table 13 Dimensions and weight in flange connection [Unit: mm] Nominal size (Inch) Pressure rating Actuator model No. K A P H G M N Weight (kg) 6 JIS10K, ANSI150, JPI150 VR3D(R) VR3HD(R) 267 420 315 740 (660) 195 320 93 116 JIS20K, ANSI300, JPI300 133 8 JIS10K, ANSI150, JPI150 VR3D(R) VR3HD(R) 292 449 315 740 (660) 195 320 93 150 JIS20K 150 ANSI300, JPI300 180 10 JIS10K, ANSI150, JPI150 VR3D(R) VR3HD(R) 330 510 315 740 (660) 195 320 93 200 JIS20K 215 ANSI300, JPI300 235 12 JIS10K, ANSI150, JPI150 VR3D(R) VR3HD(R) 356 530 315 740 (660) 195 320 93 245 JIS20K 245 ANSI300, JPI300 320 Nominal size (Inch) Mounting position of valve on process pipes (SV0512-XXX) L 6 100,101,500,501,010,011,020,021 610(530) 200,201,600,601,030,031,040,041 625(545) 300,301,700,701,050,051,060,061 640(560) 400,401,800,801,070,071,080,081 625(545) 8 100,101,500,501,010,011,020,021 605(525) 200,201,600,601,030,031,040,041 625(545) 300,301,700,701,050,051,060,061 645(565) 400,401,800,801,070,071,080,081 625(545) 10 100,101,500,501,010,011,020,021 600(520) 200,201,600,601,030,031,040,041 625(545) 300,301,700,701,050,051,060,061 650(570) 400,401,800,801,070,071,080,081 625(545) 12 100,101,500,501,010,011,020,021 595(515) 200,201,600,601,030,031,040,041 625(545) 300,301,700,701,050,051,060,061 655(575) 400,401,800,801,070,071,080,081 625(545) 4 2 |