【DO!BOOK・ページリンク】
cv-04   37 / 68

BOOKをみる

10秒後にBOOKのページに移動します


No. SS2-VFR100-0100 Azbil Corporation - 16 - Figure 11 Mounting position of valve on process pipes (Applicable to model HEP positioner) Note) 1) The pressure regulator with filter is mounted vertically to the ground. 2) Specify mounting positions other than the above standard mounting positions with code number. 3) When installing indoor, water-proof construction is not needed. 4) When the first 2 digits of the model number, which indicate the mounting angle type, are 50, 60, 70, 80, 01, 02, 03, 04, 05, 06, 07 or 08, water-proof construction is needed if installing outdoor. 5) When the first 2 digits of the model number, which indicate the mounting angle type, are 10, 20, 30 or 40, water-proof construction is not required whether it is outdoor or not. No.300 No.301 No.400 No.401 No.500 No.501 No.600 No.601 No.700 No.701 No.800 No.801 No.200 No.101 No.201 No.100 (Standard) Code number structure (Example) Model HEP Water-proof 0:No 1:Yes Mounting angle on a pipe (See figures below) No. 1 0 0