【DO!BOOK・ページリンク】 cv-04 58 / 68 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-AMT100-0100 - 5 - Note) 1) .. Positioner is necessary 2) Table care not to cause the maximum allowable differential pressure to exceed the maximum operating pressure disignated by ANSI B16.34-1981 or JIS B2201-1984. Graphite packing “P6610CH+P6528” (+230 to 350°C) Table 6 Mixing service by AMT Actuator model no. Supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Positioner Differential pressure [by port size (inches)] kPa {kgf/cm2} 3/4 1 1. 2 2. 3 4 5 6 HA2D, R 340 {3.5} 80 to 240 {0.8 to 2.4} .. 3920 {39.9} 2660 {27.1} 1800 {18.3} 1070 {10.9} 660 {6.7} 470 {4.7} 260 {2.6} HA3D, R 3200 {32.6} 1910 {19.4} 1180 {12.0} 850 {8.6} 470 {4.7} 300 {3.0} 210 {2.1} HA4D, R 2150 {21.9} 1550 {15.8} 870 {8.8} 540 {5.5} 380 {3.8} Table 7 Diverting service by AMT Actuator model no. Supply pressure kPa {kgf/cm2} Spring range kPa {kgf/cm2} Positioner Differential pressure [by port size (inches)] kPa {kgf/cm2} 3/4 1 1. 2 2. 3 4 5 6 HA2D, R 340 {3.5} 80 to 240 {0.8 to 2.4} .. 1430 {14.5} 880 {8.9} 600 {6.1} 350 {3.5} 220 {2.2} 150 {1.5} 80 {0.8} HA3D, R 1060 {10.8} 630 {6.4} 390 {3.9} 280 {2.8} 150 {1.5} 100 {1.0} 70 {0.7} HA4D, R 690 {7.0} 500 {5.0} 280 {2.8} 170 {1.7} 120 {1.2} A AB B AB A B 4 6 |