【DO!BOOK・ページリンク】 cv-06 16 / 48 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-8114-0200 - 3 - Permissible vibration 2 G / 100 Hz Output Analog feedback 4 to 20 mA (For proportional control) Contact feedback: Open/Close 2 points, contact capacity 5A, 125V AC or more. Resistance feedback: With 135 Ω potentiometer (accuracy 135 Ω 10%, linearity 1%) Manual operation With multi-turn lever Additional specifications (by special order) . Special inspection Flow characteristics inspection, material inspection (Material certificate), non-destructive inspection, steam inspection, low-temperature inspection . With drain plug . Double gland . Steam jacket . Oil/water free treatment . Stainless steel (SUS304) nuts and bolts for atmospheric exposure . Yoke material (SCPH2) . Sand-/dust preventive measure . Vacuum service Performance Rated Cv value Refer to Table 3. Flow characteristics Refer to Figure 1. Inherent rangeability Refer to Table 3. (Rangeability 75:1 is available as option for Rated Cv larger than 1.0) Allowable differential pressure Refer to Table 9 and Table 10. Leakage specification . Contoured type plug IEC 60534-4:2006 or JIS B 2005-4:2008 |