【DO!BOOK・ページリンク】 cv-07 113 / 138 10秒後にBOOKのページに移動します |
|
No. SS2-8213-0510 Azbil Corporation - 2 - Table 1 Hysteresis error and linearity [Within %F.S.] Note) When no positioner is provided, performance varies depending on the type of packing used. Output Table 2 Direct action (Downward output N) Table 3 Direct action (Upward output N) Item Spring range 20 to 98 kPa {0.2 t o1.0 kgf/cm2} 80 to 240 kPa {0.8 to 2.4 kgf/cm2} Hysteresis error Without positioner 3 5 With positioner 1 1 Linearity Without positioner ±5 ±10 With positioner HTP ±1 ±1 AVP/HEP ±1 ±1 Model number Supply pressure kPa Spring range kPa Positioner Lever position Model number Supply pressure kPa Spring range kPa Positioner Lever position |