【DO!BOOK・ページリンク】 cv-07 18 / 138 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-AVP703-0100 - 3 - PERFORMANCE SPECIFICATIONS Accuracy*1 ±1% F.S. (±2.5% with custom output characteristics) Note)*1: Refer to Table 1. Because accuracy varies depending on the combination of actuator size and travel. PHYSICAL SPECIFICATIONS Enclosure rating JISC0920 watertight, IP66 Finish Baked acrylic Color Silver Material Cast aluminum Weight Without Pressure regulator with filter: 4.2 kg With Pressure regulator with filter: 4.9 kg INSTALLATION Air connections Rc1/4 or 1/4NPT internal thread Electrical connections G1/2, 1/2NPT or M20 × 1.5 Conditions of supply air (JIS C1805-1 (2001)) Particles Maximum diameter 3 μm Oil mist Less than 1 ppm at mass Humidity of the air supply The dew point should be at least 10°C lower than the temperature of this device. Table 1 Standard travel range and accuracy Actuator Travel (mm) Accuracy [% F.S.] PSA1, 2 14.3, 20, 25 1 PSA3, 4 20, 38 1 HA1 6, 8, 10 3 14.3, 25 1 HA2 10 3 14.3, 25, 38 1 HA3 14.3 3 25, 38, 50 1 HA4 14.3 3 25, 38, 50, 75 1 VA5 25, 37.5, 50, 75, 100 1 VA6 PSA6, 7 14.3 3 25, 37.5, 50, 75, 100 1 HK1 PSK1 10 3 19 1 DAP560 1000,1000X 14.3 3 25.100 1 DAP1500 1500X 14.3, 25 3 38.100 1 7 2 |