yDO!BOOKEƒy[ƒWƒŠƒ“ƒNz cv-07@@@48 / 138 10•bŒã‚ÉBOOK‚̃y[ƒW‚Ɉړ®‚µ‚Ü‚· |
|
Azbil Corporation No. SS2-AVP300-0100 - 3 - Input resistance 300 ƒ¶ max. / 20 mA DC (Model AVP 300/301) 400 ƒ¶ typically / 20 mA DC (Model AVP 302) Output characteristics . Linear, Equal percentage, Quick opening . Custom Configurable 15 segments Stem travel range Feedback Lever Angle } 4‹ to } 20‹ Bypass operation Auto/Manual external switch (For single acting type only) Air supply pressure 140 to 700 kPa {1.4 to 7.0 kgf/cm2} Air consumption 4 l/min(N) maximum at 140 kPa {1.4 kgf/cm2} 5 l/min(N) maximum at 280 kPa {2.8 kgf/cm2} 6 l/min(N) maximum at 500 kPa {5.0 kgf/cm2} 10 l/min(N) maximum at 400 k Pa {4.0 kgf/cm2} for double acting type Maximum air deliver flowrate 110 l/min(N) at 140 kPa {1.4 kgf/cm2} 250 l/min(N) at 400 kPa {4.0 kgf/cm2} for double acting type Output balanced pressure 55 } 5% for double acting type only Lightning protection Peak value of voltage surge: 12 kV Peak value of current surge: 1000 A Vibration tolerance 2G (5 to 400 Hz) (with standard mounting kit on Azbil Corporationfs HA actuator) Ambient temperature limits -40‹C to +80‹C for general model TIIS Flameproof : -20‹C to +55‹C KOSHA Flameproof : -20‹C to +55‹C FM Explosionproof : -40‹C to +80‹C FM Intrinsically safe : -40‹C to +80‹C ISSeP/ATEX Flameproof : -20‹C to +70‹C KEMA/ATEX Intrinsically safe: -40‹C to +60‹C CSA Explosionproof : -40‹C to +80‹C NEPSI Flameproof : -40‹C to +60‹C NEPSI Intrinsically safe For Ex ia IIC T6 : -40‹C to +40‹C For Ex ia IIC T5 : -40‹C to +60‹C For Ex ia IIC T4 : -40‹C to +80‹C Ambient humidity limits 10% to 90% RH CE conformity Electromagnetic compatibility EN61326-1: 2013 (CE Marking) Configuration tools Field Communication Software CommStaff Model CFS100 PERFORMANCE SPECIFICATIONS Accuracy For 8 mA . input signal span< 16 mA } 1% F.S. (} 2.5% with custom output characteristics) For 4 mA . input signal span< 8 mA } 1.5% F.S. Travel transmission accuracy tth} 1% F.S. (}2.5% with output characteristics modification) PHYSICAL SPECIFICATIONS Enclosure classification JIS C0920 watertight, NEMA type 4X, IP66 Finish Baked acrylic Color Dark blue Material Cast aluminum Weight For single acting type Without Pressure regulator with filter : 2.5 kg With Pressure regulator with filter : 3.2 kg For double acting type Without Pressure regulator with filter : 2.8 kg With Pressure regulator with filter : 3.5 kg 7 4 |