yDO!BOOKEƒy[ƒWƒŠƒ“ƒNz cv-07@@@51 / 138 10•bŒã‚ÉBOOK‚̃y[ƒW‚Ɉړ®‚µ‚Ü‚· |
|
No. SS2-AVP300-0100 Azbil Corporation - 6 - MODEL SELECTION Basic model no. Analog signal (4 to 20 mA DC) without travel transmission. Analog signal (4 to 20 mA DC) with travel transmission. Analog signal (4 to 20 mA DC) with HART communication protocol. Note) *1 1 set of TIIS Flameproof cable gland shall be attached for model AVP300. Two sets are for model AVP301. *2 Standard finish is equal to previous Y138A. Corrosion proof is equal to previous Y138B. *3 No domestic sales in Japan due to Non-SI unit. *4 For TIIS Flameproof model, these elbows should be put on the supplied cable gland. Code gAh and gCh can not be selected simultaneously. *5 Code gEh and gNh can not be selected simultaneously. *6 Code gFh and gGh can not be selected simultaneously. *7 Select model AVP (integral type) only when the direction of drain of the pressure regulator with filter on the control valve is downward (ground). Configuration Following shows default and optional settings of each configurable parameter of AVP. Unless otherwise specified, the Smart Valve Positioner will be shipped in the following configuration. 1. Input control signal 4 to 20 mA The minimal span for custom range = 4 mA 2. Output characteristic Liner EQ or QO can be ordered or set by user. 3. Valve action Direct (Plug above seat) Reverse (Plug below seat) can be ordered or set by use 4. Output signal for position transmission 4 to 20 mA DE also selectable AVP300 - (1) (2) (3) (4) (5) - (6) (7) (8) (9) - (10) AVP301 - (1) (2) (3) (4) (5) - (6) (7) (8) (9) - (10) AVP302 - (1) (2) (3) (4) (5) - (6) (7) (8) (9) - (10) Connection Air piping Electrical connection Mounting thread Code (1) Structure Water-proof Rc1/4 G1/2 M8 X Water-proof 1/4NPT internal 1/2NPT internal 5/16-18 P Water-proof 1/4NPT internal M20 ~ 1.5 M8 Q TIIS Flameproof with cable gland *1 Rc1/4 G1/2 M8 E KOSHA Flameproof Rc1/4 G1/2 M8 S FM Explosionproof and Flameproof 1/4NPT internal 1/2NPT internal 5/16-18 F FM Intrinsically safe 1/4NPT internal 1/2NPT internal 5/16-18 M CSA Explosionproof 1/4NPT internal 1/2NPT internal 5/16-18 A ISSeP/ATEX Flameproof 1/4NPT internal M20 ~ 1.5 M8 C KEMA/ATEX Intrinsically safe 1/4NPT internal M20 ~ 1.5 M8 L NEPSI Flameproof 1/4NPT internal 1/2NPT internal 5/16-18 B NEPSI Flameproof 1/4NPT internal M20 ~ 1.5 M8 N NEPSI Intrinsically safe and Flameproof 1/4NPT internal 1/2NPT internal 5/16-18 R NEPSI Intrinsically safe and Flameproof 1/4NPT internal M20 ~ 1.5 M8 W (2) Finish Standard (Baked acrylic) *2 S Corrosion proof (Baked epoxy) *2 B Silver finish (Baked acrylic) D (3) Positioner action Direct action - Air pressure increases with control signal increase D Reverse action - Air pressure decreases with control signal increase R Air supply range Pressure gauge scale Max. regulator setting (4) Supply air pressure classification 130 |