【DO!BOOK・ページリンク】 cv-07 53 / 138 10秒後にBOOKのページに移動します |
|
No. SS2-AVP300-0100 Azbil Corporation - 8 - Note) *1 In case of double acting actuator, a reversing relay unit required. *2 Contact a sales representative if a bracket for model VFR (FloWing) or butterfly valve is required. Table 3 Mounting bracket for double acting actuator (8)(9) Mounting bracket for pneumatic actuators Code VP5, 6 *1 Y1 VP7 *1 Y7 SLOP560, 1000, 1000X *1 *2 Y2 SLOP1500, 1500X *1 *2 Y3 DAP560, 1000, 1000X *1 *2 Y4 DAP1500, 1500X *1 *2 Y5 Pentair Valve and Control Japan AK09, AK12, AK15 *1 KA Pentair Valve and Control Japan AG06, AGN06 *1 KG Pentair Valve and Control Japan AG09, AGN09 *1 KH Pentair Valve and Control Japan AG13, AGN13 *1 KJ Pentair Valve and Control Japan AW13 *1 KV Pentair Valve and Control Japan AW17 *1 KW Pentair Valve and Control Japan AW20 *1 KT KITZ B series B-2 *1 B2 KITZ B series B-3 *1 B3 KITZ B series B-4 *1 B4 KITZ B series B-5 *1 B5 KITZ B series B-6 *1 B6 Xomox (EL-O-MATIC) E25, 40, 65, 100, 200, 350 *1 RA Xomox (EL-O-MATIC) E600, 950, 1600, P2500, P4000 *1 RB Tomoe Valve Z series Z-06, 08, 11, 13 *1 EA Tomoe Valve T-matic 3I-1, 2, 3, 4 *1 E3 T. V. VALVE AT4-80 *1 V1 T. V. VALVE AT4-100 *1 V2 T. V. VALVE AT4-120 *1 V3 T. V. VALVE AT4-150 *1 V4 T. V. VALVE AT4-180 *1 V5 Table 4 Standard travel range and accuracy Actuator Travel (mm) Accuracy [% F.S.] PSA1, 2 14.3, 20, 25 1 PSA3, 4 20, 38 1 HA1 6, 8, 10 3 14.3, 25 1 HA2 10 3 14.3, 25, 38 1 HA3 14.3 3 25, 38, 50 1 HA4 14.3 3 25, 38, 50, 75 1 VA5 25, 37.5, 50, 75, 100 1 VA6 PSA6, 7 14.3 3 25, 37.5, 50, 75, 100 1 HK1 PSK1 10 3 19 1 |