No. SS2-AVP200-0100 Azbil Corporation - 2 - FUNCTIONAL SPECIFICATIONS Applicable actuator Single and double acting actuator Linear and rotary motion actuator Approvals TIIS Flameproof approval Body: Ex d IIC T6 Approval No. TC17094 Valve travel detector: Ex d IIC T6 Approval No.TC20454 Control signal input 4-20 mA DC (Configurable to any required range for split range minimum span 4 mA DC), minimum driving current: 3.85 mA. In case of model AVP201 when signal input is less than 3.85 mA output current will be burnout. Input resistance 300 ƒ¶ max. / 20 mA DC (Model AVP201/202), 400 ƒ¶ typically / 20 mA DC (Model AVP302) Output characteristics . Linear, Equal percentage, Quick opening . Custom Configurable- 15 segments Stem travel range 14.3 mm to 100 mm when feedback lever angle } 4‹ to }20‹ Bypass operation Auto / manual external switch (For single acting type only) Air supply pressure 140 to 700 kPa {1.4 to 7.0 kgf/cm2} Air consumption 4 ../min(N) maximum at 140 kPa {1.4 kgf/cm2} 5 ../min(N) maximum at 280 kPa {2.8 kgf/cm2} 6 ../min(N) maximum at 500 kPa {5.0 kgf/cm2} 10 ../min(N) maximum at 400k Pa {4.0 kgf/cm2} for double acting type Maximum air deliver rate 110 ../min(N) at 140 kPa {1.4 kgf/cm2} 250 ../min(N) at 400 kPa {4.0 kgf/cm2} for double acting type Output balanced pressure 55 } 5% for double acting type only Lightning protection Peak value of voltage surge: 12 kV Peak value of current surge: 1000A Vibration tolerance (with standard mounting kit on Azbil Corporation's HA actuator) Body: 2 G, 5 to 400 Hz Valve: 10 G, 5 to 2000 Hz Ambient temperature limits -40‹C to 80‹C TIIS Flameproof model: -20‹C to +55‹C Ambient humidity limits 10% to 90% RH Configuration tools Field Communication Software CommStaff Model CFS100 PERFORMANCE SPECIFICATIONS Accuracy } 1% F.S. (} 2.5% with custom output characteristics) Depending on cable length, the accuracy varies as follows. For 4 mA . input signal span < 8 mA, }1.5% F.S. Note) Depend on the air pipe diameter, or pipe length, the auto setup program will not properly operate. Travel transmission Accuracy } 1% F.S. (} 2.5% with output characteristics modification) Only for travel transmission type (model AVP201) PHYSICAL SPECIFICATIONS Enclosure classification JIS C0920 watertight, NEMA type 4X, IEC529 IP66 equivalent Finish Baked acrylic Color Dark blue Material Body case Cast aluminum Case of valve travel detector Stainless steel Cable Polyvinyl chloride for ambient temperature up to 80‹C Weight Body For single acting type: Without Pressure regulator with filter : 3.3 kg With Pressure regulator with filter : 4.0 kg For double acting type: Without Pressure regulator with filter : 3.6 kg With Pressure regulator with filter : 4.3 kg Valve travel detector 1.0 kg Cable 0.2 kg / 1 m Outer diameter: 9.8 mm Sheath material: PDC (PVC) Cable length Accuracy 5 m } 1.2% F.S. 10 m } 1.7% F.S. 20 m } 2.7% F.S. |