【DO!BOOK・ページリンク】 cv-07 60 / 138 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-AVP200-0100 - 3 - INSTALLATION Table 1 Examples of air purification devices Air connections Rc1/4 or 1/4NPT internal thread Electrical connections G1/2 or 1/2NPT internal thread For Travel transmission, additional wiring for the power supply is required. Conditions of supply air (JIS C1805-1 (2001)) Particles Maximum diameter 3 μm Oil mist Less than 1 ppm at mass Humidity of the air supply The dew point should be at least 10°C lower than the temperature of this device. To meet the above specifications for instrument air, install the air purification devices listed in Table 1 properly in the specified installation location. Installation location Air purification device SMC Corp. CKD Corp. Compressor outlet or main line Line filter AFF Series AF Series Mist separator AM Series Terminal device Air combination AW30 M3000 (S type) 7 5 |