No. SS2-AVP702-0100 Azbil Corporation - 2 - FUNCTIONAL SPECIFICATIONS Applicable actuator . Single and double acting actuator . Linear and rotary motion actuator Approvals TIIS Flameproof Ex d IIC T6 FM Explosionproof / Dust Ignition Protection Explosionproof (Division system):Class I, Division 1, Group B, C, D T6 . Factory sealed, conduit seal not required . Not including gasoline atmospheres Flameproof (Zone system): Class I, Zone 1, AEx d IIC Gb Dust ignition protection (Division system): ClassII, III, Division 1, Group E, F , G T6 Dust ignition protection (Zone system): Zone21 AEx tb IIIC T85 ‹C Db Enclosure classification:IP66 FMC Explosionproof / Dust Ignition Protection Explosionproof (Division system): ClassI, Division1, Group C, D T6 . Factory sealed, conduit seal not required . Not including gasoline atmospheres Flameproof (Zone system): Class I, Zone 1, Ex d IIB T6 Seal all conduits within 450 mm (18 inches) Dust ignition protection (Division system): Class II, III, Division 1, Group E, F, G T6 Enclosure classification: IP66 ATEX Flameproof / Dust Ignition Protection Flameproof: II 2 G Ex d IIC T6 Gb Dust ignition protection: II 2 D Ex tb IIIC T85 ‹C Db Enclosure classification: IP66 Cables glands or conduit sealing devices used must be sertified for the Ex d IIC protection. Use the product with the degree of protection IP66 under the IP66 required environment. IECEx Flameproof / Dust Ignition Protection Flameproof: Ex d IIC T6 Gb Dust ignition protection: Ex tb IIIC T85 ‹C Db Enclosure classification: IP66 Cables glands or conduit sealing devices used must be sertified for the IECECo Ex d IIC protection. Use the product with the degree of protection IP66 under the IP66 required environment. NEPSI Flameproof / Dust Ignition Protection Flameproof: Ex d IIC T6 Gb Dust ignition protection: DIP A21 TA 85 ‹C Enclosure classification: IP66 Cables glands or conduit sealing devices used must be sertified for the Ex d IIC or DIP A21 protection. Use the product with the degree of protection IP66 under the IP66 required environment. EAC Flameproof Flameproof: 1Ex d IIC T6 Enclosure classification: IP66 Cables glands or conduit sealing devices used must be sertified for the EAC 1Ex d IIC or IECEx Ex d IIC protection Use the product with the degree of protection IP66 under the IP66 required environment. INMETRO Flameproof / Dust Ignition Protection Flameproof: Ex d IIC T6 Gb Dust ignition protection: Ex tb IIIC T85 ‹C Db Enclosure classification: IP66 Cables glands or conduit sealing devices used must be sertified for the INMETRO or IECEx Ex d IIC or Ex td IIIC protection. Use the product with the degree of protection IP66 under the IP66 required environment. Control signal input 4.20 mA DC (Configurable to any required range for split range.) Minimum driving current: 3.84 mA Input resistance 475 ƒ¶ typically / 20 mA DC (Without the overvoltage protection) 600 ƒ¶ typically / 20 mA DC (With the overvoltage protection) Output characteristics . Linear, Equal percentage, Quick opening . Custom user characteristics (21 points) Stem travel range 14.3 to 100 mm Stroke (Feedback Lever Angle } 4‹ to } 20‹) Bypass operation Auto/Manual external switch (For single acting actuator only) Air supply pressure 140 to 700 kPa {1.4 to 7.0 kgf/cm2} Air consumption 3.2 ../min (N) maximum at 140 kPa {1.4 kgf/cm2} 4.0 ../min (N) maximum at 280 kPa {2.8 kgf/cm2} 4.8 ../min (N) maximum at 500 kPa {5.0 kgf/cm2)} 8.0 ../min (N) maximum at 400 kPa {4.0 kgf/cm2} for double acting actuator Maximum air deliver flowrate 110 ../min (N) at 140 kPa {1.4 kgf/cm2} Lightning protection Peak value of voltage surge: 12 kV Peak value of current surge: 1000 A Vibration tolerance 2 G, 5 to 400 Hz (with standard mounting kit on Azbil Corporationfs HA actuator) Ambient temperature limits -40‹C to +80‹C for general model |