【DO!BOOK・ページリンク】 cv-07 8 / 138 10秒後にBOOKのページに移動します |
|
Azbil Corporation No. SS2-AVP702-0100 - 3 - TIIS Flameproof: -20°C to +55°C FM/FMC/ATEX/IECEx/NEPSI/EAC/INMETRO Explosion protection: -30°C to +75°C Ambient humidity limits 5% to 100% RH CE conformity Electromagnetic compatibility EN61326-1: 2013 (CE Marking) PERFORMANCE SPECIFICATIONS Accuracy *1 For 8 mA . input signal span < 16 mA ±1% F.S. (±2.5% with output characteristics modification) For 4 mA . input signal span < 8 mA ±1.5% F.S. Note)*1: Refer to Table 1. Because accuracy varies depending on the combination of actuator size and travel. Travel transmission accuracy ±1% F.S. (±2.5% with output characteristics modification) PHYSICAL SPECIFICATIONS Enclosure classification JIS C0920 watertight, NEMA type 4X, IEC529 IP66 Finish Baked acrylic Color Silver Material Cast aluminum Weight Without Pressure regulator with filter: 4.2 kg With Pressure regulator with filter: 4.9 kg INSTALLATION Air connections Rc1/4 or 1/4NPT internal thread Electrical connections G1/2, 1/2NPT or M20 × 1.5 internal thread Conditions of supply air (JIS C1805-1 (2006)) Particles Maximum diameter 3 μm Oil mist Less than 1 ppm at mass Humidity of the air supply The dew point should be at least 10°C lower than the temperature of this device. 7 1 |