No. SS2-CVG100-0100 Azbil Corporation - 2 - Please read the "Terms and Conditions" from the following URL before ordering or use: http://www.azbil.com/products/bi/order.html (10) 3rd Edition: Issued in June 2012 1-12-2 Kawana, Fujisawa Kanagawa 251-8522 Japan URL: http://www.azbil.com/ Specifications are subject to change without notice. No part of this publication may be reproduced or duplicated without the prior written permission of Azbil Corporation. Air Lock Valve Model IL201-02, IL211-02 (Manufactured by SMC Co., Ltd.) If air supply to a control valve is stopped due to an abnormal pressure drop, the air pressure to the actuator becomes abnormal. An air lock valve is used to keep the valve position normal by maintaining normal air pressure. It maintains air pressure until the supply air pressure recovers to the normal level. After the air supply pressure recovers, the control valve is controlled by the normal method. SPECIFICATIONS Application Model IL201-02 used for HA, VA, and spring GOM, etc., for single-action actuator Model IL211-02 used for VP and springless GOM, etc. for double-action actuator Connection port diameter Rc1/4 Signal pressure Max. 970 kPa {9.9 kgf/cm2} Pressure setting range 140 to 690 kPa {1.4 to 7 kgf/cm2} Cutoff pneumatic circuit pressure Max. 690 kPa {7 kgf/cm2} Ambient temperature -5 to 60°C Main material Diecast aluminum Model IL201 Model IL211 Figure 2 Model IL201 installation example Figure 3 Model IL211 installation example Positioner Model IL201 OUT IN CV Input signal SIG Regulating valve with filter Positioner Model IL211 OUT1 OUT2 IN1 IN2 CV Input signal SIG Pressure regulator with filter |