Azbil Corporation No. SS2-GTX00R-0100 - 11 - F. Temperature correction function of capillary part. The change in the density (p) of fill fluid is operated.As a result, the output correction is done. The height (L) between flanges of the tank is set.Please specify it when you understand height beforehand.It is not possible to set it before shipping when height is not specified.Please apply the minus to the setting of height (L) when you set up a high pressure side under the tank. G. Installation position of Remote-sealed differential pressure transmitters. Azbil Corporation is recommended to set up the main body of the transmitter from a lower flange downward when the transmitter is set up to the sealed tank.Please meet the following requirements when it is necessary to set up the transmitter by all means in the middle of the tank. (1kpa=102mmH2O) P: Permissible pressure lower bound value of the transmitter (kPa abs.) p’: Fill fluid gravity of the transmitter Po: Pressure in tank (kPa abs.) h: Distance from a lower flange (mm) Fill fluid gravity ρ' Permissible pressure lower bound value P (kPa abs.) Temperature range of wetted parts (°C) Regular service 0.935 2 -40 to +40 High temp. 1.07 2 -5 to +90 High-temp. and vacuum 1.07 0.1333 -5 to +100 High-temp and high-vacuum 1.09 0.1333 10 to 250 Oxygen, Chlorine 1.87 54 -10 to +40 HP LP 100% level 0% level r L (m) Po + ((.(ρ'h)) . 102) . P ∴(h . (Po.P) )(102 . ρ')) 100%Level 0%Level LP HP h (mm) r' 1 6