No. SS2-GTX00U-0100 Azbil Corporation - 10 - E. Installation position of Remote-sealed differential pressure transmitters. Azbil Corporation is recommended to set up the main body of the transmitter from a lower flange downward when the transmitter is set up to the sealed tank.Please meet the following requirements when it is necessary to set up the transmitter by all means in the middle of the tank. (1kpa=102mmH2O) P: Permissible pressure lower bound value of the transmitter (kPa abs.) p’: Fill fluid gravity of the transmitter Po: Pressure in tank (kPa abs.) h: Distance from a lower flange (mm) Fill fluid gravity ρ' Permissible pressure lower bound value P (kPa abs.) Temperature range of wetted parts (°C) Regular service 0.935 2 -40 to 40 High temp. 1.07 2 -5 to 90 High-temp. and vacuum 1.07 0.1333 -5 to 100 High-temp and high-vacuum 1.09 0.1333 10 to 250 Oxygen, Chlorine 1.87 54 -10 to 40 Po + ((.(ρ'h)) . 102) . P ∴(h . (Po.P) )(102 . ρ')) 100%Level 0%Level LP HP r' h (mm) |